电工技术学报  2023, Vol. 38 Issue (zk1): 196-203    DOI: 10.19595/j.cnki.1000-6753.tces.L10103
高电压与放电 |
五种吸附剂与C4F7N气体及CF3SO2F气体的相容性试验研究
吕浥尘1,2, 郑宇1,2, 朱太云3, 周文俊1,2, 李涵1,2
1.电网环境保护全国重点实验室(武汉大学) 武汉 430072;
2.武汉大学电气与自动化学院 武汉 430072;
3.国网安徽省电力公司电力科学研究院 合肥 230601
Experimental Study on Compatibility with C4F7N and CF3SO2F Gases and Five Adsorbents
Lü Yichen1,2, Zheng Yu1,2, Zhu Taiyun3, Zhou Wenjun1,2, Li Han1,2
1. State Key Laboratory of Power Grid Environmental Protection Wuhan University Wuhan 430072 China;
2. School of Electrical Engineering and Automation Wuhan University Wuhan 430072 China;
3. State Grid Anhui Electric Power Company Limited Research Institute Hefei 230601 China
全文: PDF (1276 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 全氟异丁腈(C4F7N)和三氟甲基磺酰氟(CF3SO2F)是两种具有应用前景的SF6替代气体,有必要研究其与设备中常见吸附剂的相容性。该文通过试验研究了五种常用的吸附剂(3A分子筛、4A分子筛、5A分子筛、13X分子筛及活性氧化铝)与C4F7N气体、CF3SO2F气体的相容性,采用C4F7N/CO2、CF3SO2F/N2混合气体进行试验,检测试验前后混合气体的比例及成分,发现活性氧化铝会使C4F7N气体体积分数下降,但不会使CF3SO2F气体体积分数下降;其他几种吸附剂均不会使两种气体体积分数下降。分析表明,C4F7N气体分子的CN基团会与活性氧化铝发生弱相互作用,从而导致其被活性氧化铝吸附,因此活性氧化铝不适合作为C4F7N气体设备中的吸附剂。该文涉及的五种吸附剂均与CF3SO2F气体相容。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
关键词 吸附剂C4F7NCF3SO2FSF6替代气体相容性    
Abstract:SF6 is an advantageous insulation gas that is widely applied in electrical equipment all over the world. However, the high global warming potential (GWP) it possesses prevents it from continuous application due to environment-friendly targets. In this circumstance, a variety of environment-friendly insulation gases have entered the field of view of researchers. Perfluoroisobutyronitrile (C4F7N) and trifluoromethylsulfonyl fluoride (CF3SO2F) are two novel environment-friendly gases replacing SF6. Researchers have conducted a bunch of studies to test the dielectric properties and other properties of two gases by different methods. To promote the use of environment-friendly gases in industrial applications, it is necessary to study the compatibility between environment-friendly gases and common adsorbents in electrical equipment. Compatibility means that a kind of material will not have physical changes or chemical changes if contacted by other kinds of material. Recent research indicated that activated alumina is incompatible with C4F7N while there is little research on the compatibility of adsorbents with CF3SO2F. To find out the compatibility between the adsorbents and CF3SO2F and to verify the test methods used in this paper, a series of tests were performed.
According to the gas application scheme that the researchers have introduced, 20%C4F7N/80%CO2 mixed gas under 0.6 MPa and 40%CF3SO2F/N2 mixed gas under 0.4 MPa were used for the compatibility test. The mixed gas and the adsorbents were put into gas containers made of stainless steel at 25℃. The GC-MS tests and GC tests aimed to analyze the collected gas after the tests were performed 7 days later. The mass of the adsorbents was measured by precision balances before and after the tests to find out how much weight the adsorbent increased through the adsorption process. The gas and adsorbents test results were compared to find out if the target environment-friendly gas was adsorbed.
The adsorption effect of five commonly used adsorbents (3A molecular sieve, 4A molecular sieve, 5A molecular sieve, 13X molecular sieve, and activated alumina) on C4F7N/CO2 and CF3SO2F/N2 gases was experimentally studied. Firstly, the gas chromatography-mass spectrometry (GC-MS ) results show that there is no extra gas produced in both tests for C4F7N and CF3SO2F which indicates that there are no chemical changes during a 7-day test. By detecting the proportion and composition of mixed gases before and after the test through gas chromatography (GC) test, it is found that activated alumina can obviously reduce the proportion of C4F7N by 1.88% which can be converted to 0.257 g while no similar result was observed for CF3SO2F. Other adsorbents will not reduce the ratio of the two gases. The increased mass of the adsorbents was calculated and the increased mass of the activated alumina adsorbent is 0.282 g which is approximately equal to the decreased mass of C4F7N considering the errors in the test. Because GC-MS test result reveals that no chemical change between C4F7N and activated alumina during the test, the adsorption effect is considered physical adsorption. The analysis shows that the CN group of C4F7N molecule has a weak interaction with activated alumina, which leads to its adsorption by activated alumina. Therefore, activated alumina is not suitable for use as an adsorbent in C4F7N gas-insulated equipment, and the five adsorbents involved are all compatible with CF3SO2F.
Key wordsAdsorbent    C4F7N    CF3SO2F    SF6 alternative gases    compatibility   
收稿日期: 2023-01-10      出版日期: 2023-11-09
PACS: TM213  
基金资助:国家重点研发计划项目(2021YFB2401403)和国家电网有限公司科技项目(SGAHDK00LFJS2200332)资助
通讯作者: 郑 宇 男,1992年生,博士后,副研究员,研究方向为高电压绝缘技术。E-mail:zywhuee@whu.edu.cn   
作者简介: 吕浥尘 男,2000年生,硕士研究生,研究方向为新型环保绝缘气体。E-mail:lyceehv@whu.edu.cn
引用本文:   
吕浥尘, 郑宇, 朱太云, 周文俊, 李涵. 五种吸附剂与C4F7N气体及CF3SO2F气体的相容性试验研究[J]. 电工技术学报, 2023, 38(zk1): 196-203. Lü Yichen, Zheng Yu, Zhu Taiyun, Zhou Wenjun, Li Han. Experimental Study on Compatibility with C4F7N and CF3SO2F Gases and Five Adsorbents. Transactions of China Electrotechnical Society, 2023, 38(zk1): 196-203.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.L10103          https://dgjsxb.ces-transaction.com/CN/Y2023/V38/Izk1/196