带长连续电流多重回击作用下500kV避雷器温升特性分析
黎鹏1,2, 肖盼1,2, 屈莹莹1,2, 王宇3,4,5, 普子恒1,2, 吴田1,2
1.三峡大学电气与新能源学院 宜昌 443002;
2.湖北省输电线路工程技术研究中心(三峡大学) 宜昌 443002;
3.南瑞集团有限公司(国网电力科学研究院有限公司) 南京 211106;
4.国网电力科学研究院武汉南瑞有限责任公司 武汉 430074;
5.电网雷击风险预防湖北省重点实验室 武汉 430074
Temperature Rise Characteristics of 500kV Arrester under the Action of Multiple Return-Strokes with Long Continuous Current
Li Peng1,2, Xiao Pan1,2, Qu Yingying1,2, Wang Yu3,4,5, Pu Ziheng1,2, Wu Tian1,2
1. College of Electrical Engineering and New Energy China Three Gorges University Yichang 443002 China;
2. Hubei Provincial Engineering Technology Research Center for Power Transmission Line China Three Gorges University Yichang 443002 China;
3. NARI Group Corporation (State Grid Electric Power Research Institute) Nanjing 211106 China;
4. Wuhan NARI Limited Company State Grid Electric Power Research Institute Wuhan 430074 China;
5. Hubei Key Laboratory of Power Grid Lightning Risk Prevention Wuhan 430074 China
全文: PDF (2631 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 针对带长连续电流多重回击作用下金属氧化物避雷器(MOA)故障失效的问题,该文基于场-路耦合计算方法,研究了雷电绕击500kV直流输电线路时,长连续电流、回击幅值、回击次数和间隔时间对MOA温升特性的影响,并分析了考虑热累积效应和侧面闪络后,带长连续电流多重回击作用下MOA的温升变化。结果表明:长连续电流及多重回击间隔时间对MOA温升的影响较小,10次回击作用下MOA的最大温升可达到150.7℃,考虑热累积效应后,最大温升增大了6.6℃左右;多重回击作用下,当MOA出现单节侧闪故障时,长连续电流会使故障处电弧难以熄灭,从而导致MOA温度迅速升高,更易出现热崩溃。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
黎鹏
肖盼
屈莹莹
王宇
普子恒
吴田
关键词 多重回击长连续电流金属氧化物避雷器热累积效应温升    
Abstract:For the problem of metal oxide arrester (MOA) failure under the action of multiple return-strokes with long continuous current, based on the field-circuit coupling calculation method, the effects of long continuous current, amplitude of return-strokes, number of return-strokes and the interval time of multiple return-strokes on the temperature rise characteristics of the MOA are studied when the lightning strikes the 500kV DC transmission lines. The temperature rise of MOA under the action of multiple return-strokes with long continuous current is analyzed after considering the thermal accumulation effect and surface flashover. The results show that the long continuous current and the interval time of multiple return-strokes have little effect on the temperature rise of MOA, and the maximum temperature rise of MOA can reach 150.7℃ under the action of 10 return-strokes. After the thermal accumulation effect is considered, the maximum temperature rise increases by about 6.6℃. In the process of multiple return-strokes, when the single section surface flashover fault of the MOA occurs, the continuous current will make the fault arc unable to extinguish, which will cause the MOA temperature to rise rapidly and the thermal collapse is more likely to occur.
Key wordsMultiple return-strokes    long continuing current    metal oxide arrester (MOA)    thermal accumulation effect    temperature rise   
收稿日期: 2020-07-03     
PACS: TM862  
基金资助:国家电网公司总部科技项目(524625180018)和三峡大学学位论文培优基金项目(2020SSPY056)资助
通讯作者: 普子恒 男,1987年生,博士,副教授,研究方向为超特高压输电技术、高压电器设备绝缘试验技术。E-mail:pzhdq@ctgu.edu.cn   
作者简介: 黎 鹏 男,1989年生,博士,讲师,研究方向为输变电设备外绝缘、高压电器、电工装备多物理场分析。E-mail:lipeng_ctgu@163.com
引用本文:   
黎鹏, 肖盼, 屈莹莹, 王宇, 普子恒, 吴田. 带长连续电流多重回击作用下500kV避雷器温升特性分析[J]. 电工技术学报, 2020, 35(zk2): 603-611. Li Peng, Xiao Pan, Qu Yingying, Wang Yu, Pu Ziheng, Wu Tian. Temperature Rise Characteristics of 500kV Arrester under the Action of Multiple Return-Strokes with Long Continuous Current. Transactions of China Electrotechnical Society, 2020, 35(zk2): 603-611.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.L90224          https://dgjsxb.ces-transaction.com/CN/Y2020/V35/Izk2/603