电工技术学报  2016, Vol. 31 Issue (4): 178-186    DOI:
电力系统 |
基于单端电气量的不对称参数同塔四回线选相方法
刘琦1, 邰能灵1, 范春菊1, 于仲安2, 尚24-2014-0052/img_1.png12.611.91
1. 上海交通大学电子信息与电气工程学院 上海 200240;
2. 江西理工大学电气工程与自动化学院 赣州 341000
Fault Phase Selection Scheme for Quadruple-Circuit Transmission Lines with Asymmetrical Parameter Based on Single-Ended Electrical Quantities
Liu Qi1, Tai Nengling1, Fan Chunju1, Yu Zhongan2, Shang Jin1
1. School of Electronic Information and Electrical Engineering Shanghai Jiaotong University Shanghai 200240 China;
2. School of Electrical Engineering and Automation Jiangxi University of Science and Technology Ganzhou 341000 China
全文: PDF (502 KB)  
输出: BibTeX | EndNote (RIS)      
摘要 不对称参数的同塔四回线具有不同的自感参数,无法使用传统的12序分量法进行解耦,因此采用相线解耦法对其进行解耦,并将相电流分解为12个独立的序电流分量,解决了同塔四回线中的互感耦合问题。线路发生故障时,利用故障边界条件得到序分量之间的关系。在不同回线上发生故障时,穿越序分量与环流序分量的序电流相位分别呈现出同相或反相的特征;同一回线发生不同类型故障时,序分量电流之间满足固定的幅值关系;同一类型的不同相序故障时,序分量相位差满足特定关系。考虑故障点分布系数对保护测量装置的影响,提出适于不对称参数同塔四回线发生单回线故障时的故障识别方法,并构造了相应的选相判据,给出了选相流程和方法。PSCAD/EMTDC仿真结果表明,此选相方法具有良好的选择性,不受故障类型,故障点的位置以及过渡电阻的影响。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
刘琦
邰能灵
范春菊
于仲安
尚24-2014-0052/img_1.png12.611.9
关键词 不对称参数同塔四回线选线选相序分量单端电气量    
Abstract:The asymmetrical quadruple-circuit lines have different self-inductances, which cannot be decoupled by the twelve-sequence-component method. Phase-Line decouple method is adopted to eliminate the mutual inductance, and convert the original phase currents into 12 different independent current components. When a line fault occurs, the boundary conditions help to find out the relationship between the current components. If a fault occurs on different lines, the across components and loop components are in the same or inverse phase. The amplitudes of the components are the same while the phases are shifted a special angle during the same kind of fault on the different phase of same line. Considering the influence of the distributed factors, a fault phase selection method for asymmetrical quadruple-circuit lines is presented, flow chart for fault phase is also provided. The PSCAD/EMTDC simulation results show that this method is suitable for fault phase selection, and the fault location and fault resistance has little influence on this method.
Key wordsAsymmetrical parameter    quadruple line on the same tower    line selection    phase selection    sequence component    single terminal electric quantities   
     出版日期: 2016-03-03
PACS: TM773  
作者简介: 邰能灵 男,1972年生,教授,博士生导师,主要从事电力系统保护与控制及电力市场方向的教学与研究。E-mail: nltai@sjtu.edu.cn
引用本文:   
刘琦, 邰能灵, 范春菊, 于仲安, 尚24-2014-0052/img_1.png12.611.9. 基于单端电气量的不对称参数同塔四回线选相方法[J]. 电工技术学报, 2016, 31(4): 178-186. Liu Qi, Tai Nengling, Fan Chunju, Yu Zhongan, Shang Jin. Fault Phase Selection Scheme for Quadruple-Circuit Transmission Lines with Asymmetrical Parameter Based on Single-Ended Electrical Quantities. Transactions of China Electrotechnical Society, 2016, 31(4): 178-186.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/Y2016/V31/I4/178