电工技术学报  2022, Vol. 37 Issue (3): 655-666    DOI: 10.19595/j.cnki.1000-6753.tces.201716
电力系统与综合能源 |
有源配电网小电流接地故障暂态特征及其影响分析
秦苏亚1, 薛永端1, 刘砾钲2, 郭雨豪1, 徐铭铭3
1.中国石油大学(华东)新能源学院电气工程系 青岛 266580;
2.广西电网有限责任公司南宁供电局 南宁 530031;
3.国网河南省电力公司电力科学研究院 郑州 450052
Transient Characteristics and Influence of Small Current Grounding Faults in Active Distribution Network
Qin Suya1, Xue Yongduan1, Liu Lizheng2, Guo Yuhao1, Xu Mingming3
1. New Energy College China University of Petroleum (East China) Qingdao 266580 China;
2. Nanning Power Supply Bureau of Guangxi Power Grid Co. Ltd. Nanning 530031 China;
3. Electric Power Research Institute of State Grid Henan Electric Power Company Zhengzhou 450052 China
全文: PDF (1546 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 随着“双高(高比例清洁能源、高比例电力电子装置)电网”的普及,逆变型与旋转型分布式电源(DG)接入配电网的渗透率越来越高,其对小电流接地故障暂态特征及暂态检测的影响尚需进一步明确。该文建立了有源配电网接地故障等效电路,研究了不同DG类型(旋转型、逆变型)、接入位置及接入数量时接地故障暂态特征的变化规律,并分析其对暂态选线/定位原理与装置性能的影响。结果表明,由于DG接入不改变故障零模网络,现有利用暂态零模信号的选线与定位方法在原理上仍能适用;旋转型DG将使故障暂态电流的主谐振频率及幅值增大,衰减时间分布范围扩大,相应地,接地故障检测装置的采样频率与电流测量范围应适度增加。仿真验证了该文结果的正确性。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
秦苏亚
薛永端
刘砾钲
郭雨豪
徐铭铭
关键词 有源配电网分布式电源小电流接地故障暂态特征暂态选线暂态定位    
Abstract:With the popularization of "double high (high proportion of clean energy, high proportion of power electronic devices) power grid". The penetration rate, of inverter-type and rotating distributed power supplies (DG) into the distribution network, is getting higher. Its influence on the transient characteristics and transient detection of single-phase grounding faults need to be further clarified. In this paper, the grounding fault equivalent circuit of active distribution network is established. The variation law, of grounding fault transient characteristics under different DG types as well as different access locations and access numbers is studied. Its impact on the device performance and the principle of transient line selection and location method is analyzed. The results show that since the access of DG does not change the faulty zero-mode network, the existing line selection and location method using the transient zero-mode signal can still be applied in principle. The access of rotating DG will increase the main resonant frequency and amplitude of the fault transient current, and expands the distribution range of attenuation time. Correspondingly, the sampling frequency and current measurement range of the grounding fault detecting device should be moderately increased. Simulation and field fault data verify the correctness of the results.
Key wordsActive distribution network    distributed generation(DG)    small grounding fault    transient characteristics    transient line selection    transient fault locating   
收稿日期: 2020-12-30     
PACS: TM713  
基金资助:国家自然科学基金项目(52077221)和国家电网总部科技项目(SGHADK00PJJS1900078)资助
通讯作者: 薛永端 男,1970年生,教授,博士生导师,研究方向为配电网接地故障保护与电气安全防护。E-mail:xueyd70@126.com   
作者简介: 秦苏亚 男,1995年生,硕士研究生,研究方向为配电网接地故障检测与保护等。E-mail:qinsuya@126.com
引用本文:   
秦苏亚, 薛永端, 刘砾钲, 郭雨豪, 徐铭铭. 有源配电网小电流接地故障暂态特征及其影响分析[J]. 电工技术学报, 2022, 37(3): 655-666. Qin Suya, Xue Yongduan, Liu Lizheng, Guo Yuhao, Xu Mingming. Transient Characteristics and Influence of Small Current Grounding Faults in Active Distribution Network. Transactions of China Electrotechnical Society, 2022, 37(3): 655-666.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.201716          https://dgjsxb.ces-transaction.com/CN/Y2022/V37/I3/655