电工技术学报  2024, Vol. 39 Issue (16): 5182-5193    DOI: 10.19595/j.cnki.1000-6753.tces.231596
高电压与放电 |
温度对油-纸界面处微水迁移与局部放电的影响
刘云鹏1,2, 杨超杰1,2, 赵涛1,2, 杨家骏1,2, 刘一瑾1,2
1.华北电力大学河北省输变电设备安全防御重点实验室 保定 071003;
2.新能源电力系统全国重点实验室(华北电力大学) 北京 102206
Effect of Temperature on Moisture Migration and Partial Discharge at the Oil-Paper Interface
Liu Yunpeng1,2, Yang Chaojie1,2, Zhao Tao1,2, Yang Jiajun1,2, Liu Yijin1,2
1. Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense North China Electric Power University Baoding 071003 China;
2. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources North China Electric Power University Beijing 102206 China
全文: PDF (6052 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 变压器内部温度的改变会使油-纸绝缘中水分分布和聚集位置发生改变,而局部高含水量会严重影响油-纸绝缘的电气强度。因此,有必要研究温度对油-纸绝缘界面处微水迁移与局部放电(PD)的影响。该文利用楔形-板电极,研究了升温、起泡及降温过程中不同含水量(WC =3.61%和5.76%)的油-纸绝缘体系在水分瞬态作用下的PD特性。在温度变化过程中,持续监测油的温度、含水量和水活性,并采用升压及恒定电压法进行PD试验。试验结果表明,温度升高,油-纸界面处局部放电起始电压(PDIV)短时增加,随后PDIV开始逐渐降低且PD强度突然增强。两种含水量体系的油中含水量均逐渐增加。油浸纸板含水量越高,从纸板进入油中的水分越多。气泡出现,PDIV快速下降,油中含水量急剧增加。降温阶段,两个体系的PDIV呈现先减后增趋势,与之相对应,PD强度呈现先增后减趋势,且PD均保持在一个相对较高的水平。油温降至室温,PD并未完全消失。该研究成果对油浸式电力设备中水分的实时监测及其绝缘性能的评估具有重要理论价值。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
刘云鹏
杨超杰
赵涛
杨家骏
刘一瑾
关键词 矿物油油浸纸板微水迁移温度油-纸界面局部放电    
Abstract:The increase and decrease of internal temperature in transformers can cause changes in the distribution and accumulation of moisture in the oil-paper insulation, and high moisture content can seriously affect the electrical strength of the oil-paper insulation. Previous simulations and tests were conducted at temperatures not exceeding 80℃ and without bubble interference. Few scholars have raised the temperature to the initial temperature bubble effect to study the moisture migration and partial discharge (PD) characteristics under extreme temperature conditions. Therefore, it is necessary to study the effects of temperature changes during the heating, bubbling and cooling phases on the moisture migration and PD at the oil-paper insulation interface.
In this study, using wedge-plate electrodes, the PD characteristics of oil-paper insulation systems with different moisture content (WC = 3.61% and WC = 5.76%) were investigated under transient moisture conditions during the processes of heating, bubbling, and cooling. During the temperature change process, the temperature, moisture concentration, and moisture activity of the oil were continuously monitored, and PD tests were conducted using the voltage rise and constant voltage methods. For the voltage rise, the voltage was increased at a rate of 1 kV/(10 s) and the partial discharge inception voltage (PDIV) was measured by this method to determine the PD charge threshold for the first PD event as 100 pC. If the applied voltage reached the PDIV, it was immediately recorded and the voltage was reduced. The rest of the tests were performed at a constant voltage. All tests were performed in an electromagnetically shielded room to avoid interference with PD measurements from external activities.
The experimental results showed that as the temperature increased, the PDIV at the oil-paper interface briefly increased, followed by a gradual decrease in PDIV and a sudden increase in PD intensity. The moisture content in the oil gradually increased in both systems. The higher the moisture content in the oil-immersed paperboard was, the more moisture entered the oil. Bubbles appeared, PDIV rapidly decreased, and the moisture content in the oil sharply increased. During the cooling stage, PDIV in both systems showed a decreasing-then-increasing trend, and correspondingly, PD intensity showed an increasing-then-decreasing trend, maintaining a relatively high level. Even when the oil temperature dropped to room temperature, PD did not completely disappear. The research findings have important theoretical value for the real-time monitoring of moisture in oil-immersed electrical equipment and the evaluation of its insulation performance.
Key wordsMineral oil    oil-impregnated pressboard    moisture migration    temperature    oil-paper interface    partial discharge   
收稿日期: 2023-09-27     
PACS: TM852  
基金资助:国家电网有限公司总部科技项目资助(5500-202116119A)
通讯作者: 赵 涛 男,1982年生,讲师,研究方向为电气设备在线监测与故障诊断。E-mail:t.zhao@ncepu.edu.cn   
作者简介: 刘云鹏 男,1976年生,教授,博士生导师,研究方向为特高压输电、电气设备在线监测及故障诊断。 E-mail:liuyunpeng@ncepu.edu.cn
引用本文:   
刘云鹏, 杨超杰, 赵涛, 杨家骏, 刘一瑾. 温度对油-纸界面处微水迁移与局部放电的影响[J]. 电工技术学报, 2024, 39(16): 5182-5193. Liu Yunpeng, Yang Chaojie, Zhao Tao, Yang Jiajun, Liu Yijin. Effect of Temperature on Moisture Migration and Partial Discharge at the Oil-Paper Interface. Transactions of China Electrotechnical Society, 2024, 39(16): 5182-5193.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.231596          https://dgjsxb.ces-transaction.com/CN/Y2024/V39/I16/5182