Fault Simulation and Early Characteristics of Tail Moisture in Oil-Immigrated Paper Bushing
Dai Quanmin1,2, Qi Bo1,2, Li Chengrong1,2, Zhuo Ran3, Fu Mingli3
1. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources North China Electric Power University Beijing 102206 China; 2. Beijing Key Laboratory of High Voltage and Electromagnetic Compatibility North China Electric Power University Beijing 102206 China; 3. EPRI of China Southern Power Grid Guangzhou 510080 China
Abstract:In order to study the diagnosis and detection methods of insulation moisure for oil-impregnated paper(OIP) bushing, an OIP model with transparent sheaths was designed and a microinjection device was adopted to put deionized water into OIP model along top inner wall. The partial discharge(PD), dissipate factor, capacitance and frequency domain spectroscopy were measured after tail moisture in OIP bushing. The results presented that the capacitance was increasing with the moisture time under rated voltage ,instead of no change of tanδ and PD.The tendency of tanδ at0.001 Hz had an increasing trend for tail moisture bushing. PD might occur under 1.5 times rate voltage after tail moisture in OIP. It has the possibility of misjudgment for the moisture deposition of bushing by traditional measurement.It is suggested that the both PD under 1.5 times rate voltage and FDS should be addedfor suspected moisture bushing in off-line test.And the mearsurement of capacitance in online test should be added in order to diagnose the tail mosture of bushing earily.
戴佺民, 齐波, 李成榕, 卓然, 傅明利. 油浸纸套管尾部受潮故障模拟及早期特征[J]. 电工技术学报, 2018, 33(11): 2613-2619.
Dai Quanmin, Qi Bo, Li Chengrong, Zhuo Ran, Fu Mingli. Fault Simulation and Early Characteristics of Tail Moisture in Oil-Immigrated Paper Bushing. Transactions of China Electrotechnical Society, 2018, 33(11): 2613-2619.
[1] 张施令, 彭宗仁, 邓志祥, 等. 集总RC热网络方法应用于油气套管暂态温度计算[J]. 高电压技术, 2015, 41(7): 2294-2301. Zhang Shiling, Peng Zongren, Deng Zhixiang, et al.Application of lumped RC thermal network method in transient temperature calculation of oil/SF6 bushing[J]. High Voltage Engineering, 2015, 41(7): 2294-2301. [2] 杨丽君, 黄加佳, 许佐明, 等. 高压交流套管的油纸绝缘热老化特性及寿命模型研究[J]. 电工技术学报, 2016, 31(5):144-151. Yang Lijun, Huang Jiajia, Xu Zuoming, et al.Investigation on thermal aging characteristics and lifetime model of oil-paper insulation for HV AC bushing[J]. Transactions of China ElectrotechnicalSociety, 2016, 31(5):144-151. [3] Setayeshmehr A, Akbari A, Borsi H, et al.On-line monitoring and diagnoses of power transformer bushings[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2006, 13(3): 608-615. [4] 戴佺民, 齐波, 卓然, 等. 油浸纸套管电容芯子浸渍不良缺陷的放电过程及其特征[J]. 电工技术学报, 2017, 32(7): 181-189. Dai Quanmin, Qi Bo, Zhuo Ran, et al.Discharge process and characteristics of the poor impregnated defect of capacitor core in oil-immigrated paper bushing[J]. Transactions of China ElectrotechnicalSociety, 2017, 32(7): 181-189. [5] 彭翔, 陈禾, 夏谷林, 等. 贵广直流输电工程换流变网侧高压套管事故分析及建议[J]. 变压器, 2013, 50(9): 66-69. Peng Xiang, Chen He, Xia Gulin, et al.Analysis and suggestions of converter transformer HV line side bushing for Gui-Guang HVDC project[J].Transformer, 2013, 50(9): 66-69. [6] Dai Quanmin, Qi Bo, Zhuo Ran, et al.The influence of mass moisture invading on electrical features for oil-impregnated paper bushing[C]//2016 IEEE Conference on Electrical Insulation and Dielectric Phenomena (CEIDP),Toronto, 2016: 319-322. [7] 李明洋, 崔翔. 特高压气体绝缘开关设备套管的宽频等效电路建模[J]. 电工技术学报, 2016, 31(20): 64-72. Li Mingyang, Cui Xiang.Broadband equivalent circuit model of bushing for gas insulated switchgear in ultra high voltage substation[J]. Transactions of China Electrotechnical Society, 2016, 31(20): 64-72. [8] 王青于, 杨熙, 彭宗仁, 等. 应用三维电磁-热-流耦合场分析法计算换流变压器干式套管的温度场分布[J]. 中国电机工程学报, 2016, 36(22): 6269-6275. Wang Qingyu, Yang Xi, PengZongren, et al. 3D coupled electromagnetic-thermal-fluid method for computation of temperature field of converter transformer RIP bushings[J]. Proceedings of the CSEE, 2016, 36(22): 6269-6275. [9] 杜振波, 聂德鑫, 张连星, 等. 基于频域介电谱分析的高压套管绝缘状态评估[J]. 高压电器, 2013, 49(11): 6-11. Du Zhenbo, Nie Dexin, Zhang Lianxing, et al.Insulation evalution of high voltage bushing based on frequency domain spectrocopy analysis[J]. High Voltage Apparatus, 2013, 49(11): 6-11. [10] 白帆. 基于频域介电谱的油纸绝缘套管受潮与老化状态诊断研究[D]. 西安: 西安交通大学, 2015. [11] 董明, 王丽, 吴雪舟, 等. 油纸绝缘介电响应检测技术研究现状与发展[J]. 高电压技术, 2016, 42(4): 1179-1189. Dong Ming, Wang Li, Wu Xuezhou, et al.Status and progress in study of dielectric response technology for oil-paper insulation[J]. High Voltage Engineering, 2016, 42(4): 1179-1189. [12] 吴雄. 基于FDS的油纸绝缘设备模型参数辨识及状态关联研究[D]. 重庆: 重庆大学, 2016. [13] Fofana I, Hemmatjou H, Meghnefi F, et al.On the frequency domain dielectric response of oil-paper insulation at low temperatures[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2010, 17(3): 799-807. [14] 戴佺民, 齐波, 卓然, 等. 油浸纸套管电容芯子极板边缘电场分布的仿真及优化方法[J]. 电网技术, 2017, 41(5): 1683-1688. Dai Quanmin, Qi Bo, Zhuo Ran, et al.Electric field simulation and optimization methods of capacitor core foil edge of oil-impregnated paper bushing[J]. Power System Technology, 2017, 41(5): 1683-1688.