Analog Experiment on the Relationship Between the Intensity of Epoxy Solid Insulation Surface Discharge and the Increasing Law of Characteristic Gases in GIS
1.Guangdong Power Grid Co. Ltd. Electric Power Research Institute Guangzhou 510080 China 2.School of Electrical Engineering Wuhan University Wuhan 430072 China
Abstract:In order to establish the relationship between the intensity of solid epoxy insulation surface discharge in SF6 equipment and the increasing law of characteristic gases,corresponding defect model with copper attached to the surface is set up in this paper.It is found in the experiment that different gases present different growth characteristics,even the same gas takes on different growth characteristics under different discharge strength.The ratio between the concentration of different gases and CS2 is studied,which presents totally different characteristics withdifferent levels of discharge.The species,concentration and trends over time of characteristic gases under tow levels of discharge are compared.The gases include SOF2,SO2,CS2 etc.,which are generated under two different discharge intensities.By studying the relationship between the gases and the discharge strength,and the inherent relationship between the gases,the state of internal solid insulation can be diagnosed using characteristic gas analysis.
郑晓光,郑 宇,唐 念,李 丽,周文俊. GIS内环氧树脂绝缘沿面放电强度与产气关联规律的模拟实验[J]. 电工技术学报, 2015, 30(17): 172-179.
Zheng Xiaoguang,Zheng Yu,Tang Nian,Li Li,Zhou Wenjun. Analog Experiment on the Relationship Between the Intensity of Epoxy Solid Insulation Surface Discharge and the Increasing Law of Characteristic Gases in GIS. Transactions of China Electrotechnical Society, 2015, 30(17): 172-179.
[1] 严璋,朱德恒.高电压绝缘技术[M].第二版.北京:中国电力出版社,2007:148-168. [2] 李丽,陈俊,姚唯建,等.基于模拟实验的SF6电气设备低能量放电形式的特征气体[J].高压电器,2011,47(11):15-19. Li Li,Cheng Jun,Yao Weijian,et al.Characteristic gas for estimating the type of low energy discharge in GIS based on simulated experiment[J].High Voltage Apparatus,2011,47(11):15-19. [3] 张晓星,姚尧,唐炬,等.SF6放电分解气体组分分析的现状和发展[J].高电压技术,2008,34(4):664-669,747. Zhang Xiaoxing,Yao Yao,Tang Ju,et al.Actuality and perspective of proximate analysis of SF6 decomposed products under partial discharge[J].High Voltage Engineering,2008,34(4):664-669,747. [4] 高文胜,钱政,严璋.电力变压器固体绝缘故障的诊断方法[J].高电压技术,1999,25(1):26-28. GaoWensheng,Qian Zheng,Yan Zhang.Fault diagnosis method for solid insulation of power transformer[J].High Voltage Engineering,1999,25(1):26-29. [5] GB/T 7252—2001,变压器油中溶解气体分析和判断导则[S].北京:中华人民共和国国家质量监督检验检疫总局,2001. [6] Chu F Y.SF6 decomposition in Gas-insulated equipment[J].IEEE Transactions on Electrical Insulation,1986,EI-21(5):693-725. [7] 刘有为,吴立远,弓艳朋.GIS设备气体分解物及其影响因素研究[J].电网技术,2009,33(5):58-61. Liu Youwei,Wu Liyuan,Gong Yanpeng.Inverstigation on SF6 decomposition products in GIS and affecting factors[J].Power System Technology,2009,33(5):58-61. [8] 唐炬,任晓龙,谭志红,等.针-板缺陷模型下局部放电量与SF6分解组分的关联特性[J].高电压技术,2012,38(3):527-534. Tang Ju,Ren Xiaolong,Tan Zhihong,et al.Correlation character between partial discharge quantity and SF6 decomposition components under needle-plate defect model[J].High Voltage Engineering,2012,38(3):527-534. [9] Van Brunt R J,Herron J T.Fundamental processes of SF6 decomposition and oxidation in glow and corona discharges[J].IEEE Transactions on Electrical Insulation,1990,25 (1):75-94. [10]颜湘莲,王承玉,季严松,等.开关设备中SF6气体分解产物检测的应用[J].电网技术,2010,34(9):160-165. Yan Xianglian,Wang Chengyu,Ji Yansong,et al.Application of decomposition products detection of SF6 in switchgears[J].Power System Technology,2010,34(9):160-165. [11]裘吟君,袁静帆,陈晓琳.SF6新气痕量杂质对SF6电气设备寿命的影响[J].高电压技术,2013,39(2):360-364. Qiu Yinjun,Yuan Jingfan,Chen Xiaolin.Influence of trace impurities from SF6 new gas on the life of SF6 insulation electrical equipment[J].High Voltage Engineering,2013,39(2):360-364. [12]Chen J,Zhou W J,et al.Insulation condition monitoring of epoxy spacers in GIS using a decomposed gas CS2[J].IEEE Transactions on Dielectrics and Electrical Insulation,2013,20(6):2152-2157. [13]陈俊.基于气体分析的SF6电气设备潜伏性缺陷诊断技术研究及应用[D].武汉:武汉大学,2014. [14]Nitta T,Shibuya Y,Fu jiwara Y,et al.Factors controlling surface flashover in SF6 gas insulated systems[J].IEEE Transactions on Power Apparatus and Systems,1978,97(3):959-968. [15]Tang Ju,Liu Fan,Zhang Xiaoxing,et al.Partial discharge recognition through an analysis of SF6 decomposition products part 1:decomposition characteristics of SF6 under four different partial discharges[J].IEEE Transactions on Dielectrics and Electrical Insulation,2012,19(1):29-36. [16]IEC 60270,High-voltage test techniques-Partial discharge measurements[S].2000. [17]GB/T 7354—2003,局部放电测量[S].北京:中华人民共和国家质量监督检验检疫总局,2003. [18]DL/T 639—1997,六氟化硫电气设备运行、实验及检修人员安全防护细则[S].北京:电力工业部,1997. [19]刘帆.局部放电下六氟化硫分解特性与放电类型辨识及影响因素校正[D].重庆:重庆大学,2013. [20]王宇,李智,姚唯健,等.广东省220 kV及以上GIS SF6分解产物分析[J].高电压技术,2009,35(4):823-827. Wang Yu,Li Zhi,Yao Weijian,et al.Analysis of SF6 byproducts of gas insulated switchgear (220 kV and above) in Guangdong province[J].High Voltage Engineering,2009,35(4):823-827.