电工技术学报  2023, Vol. 38 Issue (23): 6305-6317    DOI: 10.19595/j.cnki.1000-6753.tces.221559
电力系统与综合能源 |
基于并网电流谐波微分的有源阻尼策略
杨树德1, 李旺1, 徐佳1, 张新闻2, 熊连松3
1.扬州大学电气与能源动力工程学院 扬州 225127;
2.北方民族大学电气信息工程学院 银川 750021;
3.电力设备电气绝缘国家重点实验室(西安交通大学) 西安 710049
Research on Active Damping Strategy Based on the Differentiation of Injected Grid Current Harmonics
Yang Shude1, Li Wang1, Xu Jia1, Zhang Xinwen2, Xiong Liansong3
1. College of Electrical, Energy and Power Engineering Yangzhou University Yangzhou 225127 China;
2. School of Electrical and Information Engineering North Minzu University Yinchuan 750021 China;
3. State Key Laboratory of Electrical Insulation and Power Equipment Xi'an Jiaotong University Xi'an 710049 China
全文: PDF (2011 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 采用有源阻尼抑制弱电网下并网变流器系统失稳振荡的方法近年来受到广泛关注。已有的直接以公共耦合点(PCC)电压为反馈量的有源阻尼方法可有效抑制系统的失稳振荡,但会削弱系统对电网背景谐波电压扰动的抑制能力,进而影响到并网电流质量。为此,该文提出一种基于并网电流谐波微分的有源阻尼策略,通过微分运算将系统失稳振荡引发的谐振电流转换成PCC处的谐振电压,避免了将电网背景谐波电压扰动引入到并网电流参考值,可兼顾弱电网下并网变流器系统稳定控制和高质量并网电流两方面需要。仿真和实验结果验证了该文中理论分析的正确性和所提控制策略的有效性。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
杨树德
李旺
徐佳
张新闻
熊连松
关键词 弱电网并网变流器失稳振荡有源阻尼并网电流谐波微分    
Abstract:The active damping strategy that simulates a virtual resistor at the point of common coupling (PCC) is effective to improve the converter stability under weak grid. However, in the traditional strategy, the PCC voltage is generally fed to the current reference by multiplying a gain. Naturally, the disturbances of grid background harmonic voltages will be also introduced to the current reference, and the unexpected harmonics will arise in the current. Thus, the traditional strategy will weaken the rejection abilities of the converter on the background harmonic voltages and reduce the current quality. To solve these issues, this paper proposes an active damping strategy based on the differentiation of injected grid current harmonics, which can ensure the system stability and the current quality simultaneously.
First, the control structure of the active damping strategy based on the differentiation of injected grid current harmonics is given, in which the differential operation is used to transfer the harmonic currents to the harmonic voltages. This way, only the harmonic voltages caused by the unstable resonance will be fed to the output current reference, and the grid background harmonic voltages can be excluded. Therefore, the disturbances in the output current reference from grid background harmonic voltages can be eliminated and the output current quality will not be influenced by the active damping control. In addition, the rejection abilities of the converter on the background harmonic voltage disturbances before and after applying the proposed active damping strategy are compared.
Simulation and experimental results show that, with the proposed active damping strategy, the minimum short circuit ratio (SCR) for the grid-connected converter system to operate stably is reduced from 20 to 2.9, which indicates that the proposed method can markedly improve the adaptability of the converter to weak grid condition. Moreover, under a distorted grid voltage condition, the comparison of current total harmonic distortion (THD) with the different active damping methods shows that, the current THDs are 2.18% (simulation result) and 2.11% (experimental result) with the proposed method, while the current THDs are 3.3% (simulation result) and 3.0 (experimental result) with the conventional method. This demonstrates that the proposed active damping method can obtain higher current quality compared to the conventional method. This is because the rejection abilities of the converter on the background harmonic voltage disturbances can remain unchanged when the proposed active damping method is used.
The following conclusions can be drawn from the simulation and experimental analysis: (1) If the grid impedance is not considered, the larger grid inductance of weak grid may affect the converter stability and even to destabilize the system. (2) The active damping strategy based on PCC voltage feedback can improve the stability of the converter under weak grid. However, it will introduce the disturbances of background harmonic voltages to the current reference and weaken the rejection abilities of the converter on these disturbances, thereby reducing the current quality. (3) For the active damping strategy based on the differentiation of injected grid current harmonics, the differential operation is used to transfer the resonant current caused by the instability to the resonant voltage at PCC. Therefore, the disturbances in the current reference from background harmonic voltages can be avoided. The proposed method can realize the active damping performance, and meanwhile, the rejection abilities of the converter on the background harmonic voltages will not be weakened. Both the stability control of the converter system under weak grid and the high quality of grid-injected current can be satisfied.
Key wordsWeak grid    grid-connected converter    unstable oscillation    active damping    differentiation of injected grid current harmonics   
收稿日期: 2022-08-11     
PACS: TM46  
基金资助:江苏省高等学校自然科学基金(19KJB470038)、宁夏自然科学基金(2020AAC03210)和国家自然科学基金(51867001)资助项目
通讯作者: 杨树德 男,1986年生,博士,讲师,硕士生导师,研究方向为可再生能源发电系统并网控制及稳定性分析。E-mail:358060069@qq.com   
作者简介: 李旺 男,1996年生,硕士研究生,研究方向为弱电网下并网变流器系统的稳定性分析与增强控制。E-mail:735987495@qq.com
引用本文:   
杨树德, 李旺, 徐佳, 张新闻, 熊连松. 基于并网电流谐波微分的有源阻尼策略[J]. 电工技术学报, 2023, 38(23): 6305-6317. Yang Shude, Li Wang, Xu Jia, Zhang Xinwen, Xiong Liansong. Research on Active Damping Strategy Based on the Differentiation of Injected Grid Current Harmonics. Transactions of China Electrotechnical Society, 2023, 38(23): 6305-6317.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.221559          https://dgjsxb.ces-transaction.com/CN/Y2023/V38/I23/6305