高湿条件下基于凝露分布模型的导线电晕起始电压预测
胡琴1, 何高辉1, 彭华东2, 李永福2, 舒立春1
1.输配电装备及系统安全与新技术国家重点实验室(重庆大学)重庆400044;
2.国网重庆市电力公司电力科学研究院重庆401123
Prediction of Conductor Corona Onset Voltage Based on Condensation-Distribution Model under High Humidity Conditions
Hu Qin1, He Gaohui1, Peng Huadong2, Li Yongfu2, Shu Lichun1
1. State Key Laboratory of Power Transmission Equipment & System Security and New Technology Chongqing University Chongqing400044 China;
2. State Grid Electric Power Research Institute of Chongqing Electric Power Company Chongqing 401123 China
全文: PDF (24500 KB)  
输出: BibTeX | EndNote (RIS)      
摘要 湿度是影响导线电晕起始电压的重要因素,基于四热阻换热模型和分形理论建立适用于高湿度条件下导线的凝露分布模型,计算得到不同湿度和导线温度配合下导线表面凝露的尺寸和分布规律,计算结果与金相显微镜下凝露试验测量结果相差很小。通过有限元方法由凝露分布模型得出的参数计算得到凝露时导线表面的电场分布;代入导线电晕放电的光电离模型计算得到电晕起始电压的预测值。研究表明:相对湿度越高,导线温度与环境温度相差越大,电晕起始电压下降越明显,在相对湿度高于80%后,电晕起始电压趋于饱和。试验得到的不同凝露条件下导线的电晕起始电压和预测值的误差小于5%。因此,所提方法可应用于高湿度条件下导线电晕起始电压的预测。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
胡琴
何高辉
彭华东
李永福
舒立春
关键词 凝露导线电晕起始电压凝露分布模型高湿度    
Abstract:Humidity has a significant influence on the corona onset voltage of conductor.The presented paper constructs a condensation-distribution model based on quadri-thermal resistance heat transfer model and fractal theory under high humidity circumstance, and calculates the dimensions of the maximum dewdrop and the distribution regularities of dewdrop under various conductor temperature and humidity conditions, which are agree with the test results of metallographic microscope. The parameters derived from the condensation-distribution model are used to calculate the electric field intensity distribution of conductors, and input the results of electric field intensity distribution into a corona photoionization model to obtain the corresponding corona onset voltage.The higher of the humidity or the temperature differences between conductor and circumstance, the smaller of the corona onset voltage, and when the relative humidity reaches 80%, the corresponding corona inception voltage tends to saturate. Comparing the prediction results of corona onset voltage with experiments results, the errors are less than 5%. Therefore, the proposed method could be applied on the corona onset voltage prediction of conductors under high humidity circumstance.
Key wordsCondensation    conductor    corona onset voltage    condensation-distribution model    high humidity   
收稿日期: 2017-02-08      出版日期: 2018-04-12
PACS: TM726  
基金资助:国家电网重庆市电力公司科研项目(SGCQDK00PJJS1600049)和国家自然科学基金专项基金创新群体基金(51321063)资助
通讯作者: 何高辉男,1992年生,博士研究生,研究方向为复杂大气环境下输电线路电晕放电。E-mail:hegaohui@cqu.edu.cn   
作者简介: 胡琴男,1981年生,博士,教授,研究方向为电气工程领域高电压与绝缘技术。E-mail:huqin@cqu.edu.cn
引用本文:   
胡琴, 何高辉, 彭华东, 李永福, 舒立春. 高湿条件下基于凝露分布模型的导线电晕起始电压预测[J]. 电工技术学报, 2018, 33(7): 1634-1640. Hu Qin, He Gaohui, Peng Huadong, Li Yongfu, Shu Lichun. Prediction of Conductor Corona Onset Voltage Based on Condensation-Distribution Model under High Humidity Conditions. Transactions of China Electrotechnical Society, 2018, 33(7): 1634-1640.