电工技术学报  2017, Vol. 32 Issue (13): 137-144    DOI: 10.19595/j.cnki.1000-6753.tces.151972
电工理论 |
基于极性变化直流电压源的铁磁元件铁心剩磁通测量方法
刘涛1, 刘鑫2, 梁仕斌3, 王俊凯2, 姚陈果2
1. 云南电力技术有限责任公司 昆明 650217;
2. 输配电装备及系统安全与新技术国家重点实验室(重庆大学) 重庆 400044;
3. 云南电力试验研究院(集团)有限公司 昆明 650217
Residual Flux Measuring Method on the Core of Ferromagnetic Components Based on Alternating Polarity DC Voltage Source
Liu Tao1, Liu Xin2, Liang Shibin3, Wang Junkai2, Yao Chenguo2
1. Yunnan Electric Power Technology Company Kunming 650217 China;
2. State Key Laboratory of Power Transmission Equipment & System Security and New Technology Chongqing University Chongqing 400044 China;
3. Yunnan Electric Power Test & Research Institute Co. Ltd Kunming 650217 China
全文: PDF (20900 KB)  
输出: BibTeX | EndNote (RIS)      
摘要 剩磁通可能给变压器带来较大的励磁涌流,影响测量互感器的测量精度。然而目前对于变压器的铁心剩磁通测量还没有规范的方法。为了便捷地测量铁心剩磁通,提出一种采用极性变化的直流电压源来测量铁磁元件铁心剩磁通和剩磁系数的方法。该方法采用半桥电路获得极性变化的直流电压,并施加在绕组两端,使铁心分别达到正、负饱和点。绘制整个过程中的磁通与电流关系曲线,即可得到铁心的部分饱和磁滞回线,根据获得的饱和磁滞回线来计算铁心剩磁通和剩磁系数。并且在电流互感器上开展实验,测得在正、负饱和剩磁点和退磁后的磁通零点的剩磁通平均值分别为4.001mWb、-3.844mWb和0.048mWb。结果表明,该方法具有较高的准确性和稳定性,而且需要的退磁电源功率小,方便携带。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
刘涛
刘鑫
梁仕斌
王俊凯
姚陈果
关键词 剩磁通 剩磁系数 励磁涌流 剩磁测量 磁滞回线    
Abstract:Residual flux may cause strong inrush current on transformers and affect measuring accuracy of current transformer (CT). Nowadays, measurement of residual flux of transformer core, however, is not standardized. Owing to the convenience of residual flux measurement, alternating polarity DC voltage source, which is used for characterizing residual flux and magnetic remanence coefficient of ferromagnetic core, is demonstrated in this paper. By applying alternating polarity DC voltage generated by half-bridge circuit on windings, negative and positive saturation points of ferromagnetic core are reached, respectively. The saturated part of hysteresis loop is obtained via plotting magnetic flux-current curve during the whole process. Residual flux and magnetic remanence coefficient are then calculated based on the obtained hysteresis loop. In addition, investigation was conducted on the current transformer, and residual flux was measured on positive and negative saturation points along with zero flux point. The average values are 4.001mWb, -3.844mWb and 0.048mWb, respectively. These results show high accuracy and stability of this method. Besides, the rated power of demagnetization voltage source is low which makes the demagnetization devices more portable.
Key wordsResidual flux    remanence coefficient    inrush current    measuring of residual flux    hysteresis loop   
收稿日期: 2015-12-07      出版日期: 2017-07-19
PACS: TM452  
基金资助:中国南方电网有限责任公司科技项目资助(K-YN2014-136)
通讯作者: 刘 鑫 男,1992年生,硕士研究生,研究方向为互感器及变压器设备检测方法。E-mail: alxenderking@cqu.edu.cn   
作者简介: 刘 涛 男,1981年生,本科,工程师,研究方向为互感器及高电压测试设备检测技术。E-mail: 14607094@qq.com
引用本文:   
刘涛, 刘鑫, 梁仕斌, 王俊凯, 姚陈果. 基于极性变化直流电压源的铁磁元件铁心剩磁通测量方法[J]. 电工技术学报, 2017, 32(13): 137-144. Liu Tao, Liu Xin, Liang Shibin, Wang Junkai, Yao Chenguo. Residual Flux Measuring Method on the Core of Ferromagnetic Components Based on Alternating Polarity DC Voltage Source. Transactions of China Electrotechnical Society, 2017, 32(13): 137-144.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.151972          https://dgjsxb.ces-transaction.com/CN/Y2017/V32/I13/137