Abstract:Nowadays the automatic control device for voltage and reactive power is mainly implemented in 110kV or lower voltage level substations, which aims at controlling the voltage of low-voltage side and the power factor of high-voltage side. For 220kV substations with three voltage ranks, this paper offers a new approach of voltage and var integrated control based on MCR and MSVC. Considering the interaction between each side of the transformer, this method focuses on the bus voltage of three different voltage levels and the power factor of high-voltage side. Simulation model consisting of two main transformers with MCR at medium-voltage side and MSVC at low-voltage side based on Matlab/Simulink is established. And this simulation is compared with simulation of only installs MSVC in the low voltage side and only installs MCR in medium voltage side. Simulation results indicate the effectiveness in achieving qualified voltage at each side and general reactive power balance under different operating modes of the method of coordinately controlling medium and low voltage side.
陈柏超,宋继明,周攀,倪向萍,张亚迪,袁佳歆. 基于MCR和MSVC的220kV变电站多电压等级无功电压综合控制[J]. 电工技术学报, 2015, 30(16): 230-237.
Chen Baichao,Song Jiming,Zhou Pan,Ni Xiangping,Zhang Yadi,Yuan Jiaxin. MCR and MSVC Based Voltage and Reactive Power Combination Control of Different Voltage Level in 220kV Substation. Transactions of China Electrotechnical Society, 2015, 30(16): 230-237.
[1] 吕志鹏, 罗安, 帅智康, 等. 变电站无功电压协同优化及复合控制系统研究[J]. 中国电机工程学报, 2009, 29(34): 50-56. Lü Zhipeng, Luo An, Shuai Zhikang, et al. Reactive power and voltage optimized composite control for power substation[J]. Proceedings of the Chinese Society of Electrical Engineering, 2009, 29(34): 50-56. [2] 张宇, 陈乔夫, 程路, 等. 基于磁通补偿的高压大容量可控电抗器[J]. 电工技术学报, 2009(3): 93-98. Zhang Yu, Chen Qiaofu, Cheng Lu, et al. Based on magnetic-flux controllable reactor of high voltage large capacity to compensate[J]. Transactions of China Electrotechnical Society, 2009(3): 93-98. [3] Chen Baichao, Kokernak J M. Thyristor controlled two-stage magnetic-valve reactor for dynamic var- compensation in electric railway power supply systems [C]. Proceedings of the IEEE 2000 Applied Power Electronics Conference, 2000. [4] Jin Xi, He Sheng, Gao Liang. Comprehensive voltage & reactive power control in substation based on adaptive computation of very-short-term forecast[C]. Proceedings of POWERCON 2002: 1990-1994. [5] Danilo Hernane Spatti, Ivan Nunes da Silva, Wesley Fernando Usida, et al. Real-time voltage regulation in power distribution system using fuzzy control[J]. IEEE Transactions on Power Delivery, 2010, 25(2): 1112- 1123. [6] Chen Huaizhong. Research and application in substation reactive power dynamic compensation based on fuzzy control[C]. Sixth International Conference on Fuzzy Systems and Knowledge Discovery, FSKD’09, 2009, 4: 140-144. [7] 张勇军, 张豪, 杨雄平. 解决超调问题的220kV变电站无功配置方法[J]. 电网技术, 2012, 36(9): 193-197. Zhang Yongjun, Zhang Hao, Yang Xiongping. A con- figuration method of reactive power compensation for 220kV substations to reduce voltage overshoot[J]. Power System Technology, 2012, 36(9): 193-197. [8] Xu Zigang, Wang Fei. Research on fuzzy logic based dynamic boundary voltage and reactive power integrated control method[C]. Control and Decision Conference, CCDC’09, 2009: 1645-1649. [9] Li Peng, Xue Jinming, Li Yuwei, et al. Research on dynamic voltage and reactive power control system based on sixteen-area diagram control strategy[C]. 2012 IEEE International Conference on the Power System Technology(POWERCON), 2012: 1-6. [10] Shi Huan, Sun Meng, Li Wenjie. Research of reactive power and voltage integrated control in substation based on new type SVC[C]. 2012 IEEE Power Engineering and Automation Conference(PEAM), 2012: 1-4. [11] 陈刚, 马爱军, 张继红, 等. AVC分散控制模式下的变电站电压无功综合控制研究[J]. 电网技术, 2010, 34(12): 187-192. Chen Gang, Ma Aijun, Zhang Jihong, et al. Voltage and reactive power control in substation under decen- tralized control mode of AVC[J]. Power System Technology, 2010, 34(12): 187-192. [12] 郭庆来, 孙宏斌, 张伯明, 等. 自动电压控制中连续变量与离散变量的协调方法[J]. 电力系统自动化, 2008, 32(8): 39-42. Guo Qinglai, Sun Hongbin, Zhang Boming, et al. Coordination of continuous variables and discrete variables in automatic voltage control[J]. Automation of Electric Power System, 2008, 32(8): 39-42. [13] Abdel-Rahman M H, Youssef F M H, Saber A A. New static var compensator control strategy and coordination with under-load tap changer[J]. IEEE Transactions on Power Delivery, 2006, 21(3): 1630-1635. [14] Dai Jing, Wang Jun, et al. Reactive power-voltage integrated control method based on MCR[C]. Procee- dings of the Control Automation and Systems(ICCAS), 2010: 727-731.