Abstract:Results of experiment and simulation show that low-frequency oscillation will come forth in a standalone generator-rectifier system with capacitor-resistor load when its system parameters are not reasonable. This paper detailedly studies the issue by the methods of theory computation, experiment and simulation. The system state-space model must be built firstly to finish the theory computation, which includes the simplified 2-dimension model of generator, the dynamic average-value model of diode-bridge rectifier and dynamic model of load. Then the small-signal model of system will be obtained by the linearing method at a steady-state operation point. And finally the eigenvalue theory is used to estimate the system stability. On the ground of the experiments, simulations and theory computation, this paper summarizes the law of steady-state stability of such system, analyzes the physics mechanism, and presents the control methods for the issue from points of view of parameters and controller.
魏克银, 徐俊霞, 韩辉, 蒋云昊. 带阻容负载的独立发电机整流系统的静态稳定性研究[J]. 电工技术学报, 2012, 27(10): 228-234.
Wei Keyin, Xu Junxia, Han Hui, Jiang Yunhao. Study on Steady-State Stability of Generator-Rectifier System with Capacitor-Resistor Load. Transactions of China Electrotechnical Society, 2012, 27(10): 228-234.
[1] IEEE Committee Report. IEEE standard definitions for excitation systems for synchronous machines[S]. IEEE Std 421.1™—2007, July 2007. [2] Warner T H Kassakian J G. Transient characteristics of large turboalternator driven rectifier/inverter system based on field test data[J]. IEEE Transactions on Power Apparatus Systems, 1985, 104(7): 1804-1811. [3] Sudhoff S D, Coorzine K A, Glover S F, et al. DC link stabilized field oriented control of electric propulsion systems[J]. IEEE Transactions Energy Conversion, 1998, 13(1): 27-33. [4] 郭云珺, 王东, 刘德志, 等. 变频驱动三相感应电机系统稳定性的数学推导与分析[J]. 电工技术学报, 2010, 25(9): 47-55. Guo Yunjun, Wang Dong, Liu Dezhi, et al. Mathematical deduction and stability analysis of three-phase inverter-fed induction motor drive system[J]. Transactions of China Electrotechnical Society, 2010, 25(9): 47-55. [5] 马伟明. 十二相同步发电机及其整流系统的研究[D]. 北京: 清华大学, 1995. [6] 张晓锋. 同步发电机整流系统的运行稳定性研究[D]. 北京: 清华大学, 1995. [7] 杨青. 交直流混合独立供电系统运行稳定性研究[D]. 武汉: 海军工程大学, 2003. [8] Wu Xusheng, Ma Weiming, Sun Junzhong, et al. Parameter measurement of multi-phase synchronous machines with AC and DC output[C]. Proceedings of the 5th International Conference on Electrical Machines and Systems, Shenyang, 2001: 587-591. [9] Ma Weiming, Hu An, Liu Dezhi, et al. Stability of a synchronous generator with diode-bridge rectifier and back-EMF load[J]. IEEE Transactions Energy Convetsion, 2000, 15(4): 458-463. [10] 陈明亮. 电力电子变换器端口特性分析及应用研究[D]. 武汉: 海军工程大学, 2007. [11] Belkhayat M. Stability criteria for AC power systems with regulated loads[D]. Indiana: Purdue University, 1997. [12] Sudhoff S D, Glover S F, Lamm P T, et al. Admittance space stability analysis of power electronic systems[J]. IEEE Transactions Aerospace Electronics System, 2000, 36(3): 965-973. [13] Sudhoff S D, Corzine K A, Hegner H J, et al. Transient and dynamic average-value modeling of synchronous machine fed load-commutated converters[J]. IEEE Transactions on Energy Conversion, 1996, 11(3): 508-514. [14] Huiyu Z, Burgos R P, Lacaux F, et al. Evaluation of average models for nine-phase diode rectifiers with improved AC and DC dynamics[C]. Proceedings of the 21st IEEE Annual Conference on Applied Power Electronics Conference and Exposition, Dallas, TX, USA, 2006: 1324-1330. [15] Alt J T, Sudhoff S D, Ladd B E, Analysis and average-value modeling of an inductorless synchronous machine load commutated converter system[J]. IEEE Transactions Energy Conversion, 1999, 14(1): 37-43. [16] Simulink—Writing S-Functions, 6th ed. [Z]. The Math Works, Inc., Natick, MA, 2002: 2-9-2-12. [17] Sanders S R, Verghese G C. Synthesis of averaged circuit models for switched power converters[J]. IEEE Transactions on Circuits and Systems, 1991, 38(8): 905-915.