Abstract  Based on the test model of single-phase four-column transformer, the temperature rise test under DC bias was carried out, and the variation law of measuring point temperature was obtained. The model for temperature field calculation was established, and the expression of heat transfer coefficient on the surface of structural was given. Considering the change of material parameters of oil with temperature, the heat transfer coefficient was solved as one of the unknown variables. The temperature distribution of structural parts under DC bias was calculated. The temperature relative error between the simulation results and the measurement results are small, which verifies the correctness of the calculation model and the calculation method.
Key wordsDC bias      loss      heat transfer coefficient      temperature distribution     
Received: 27 March 2020     
PACS: TM401  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Wang Zezhong
Li Mingyang
Xuan Mengzhen
Huang Tianchao
Li Bing
Cite this article:   
Wang Zezhong,Li Mingyang,Xuan Mengzhen等. Temperature Rise Test and Simulation of Single-Phase Four-Column Transformer under DC-Bias[J]. Transactions of China Electrotechnical Society, 2021, 36(5): 1006-1013.
URL:  
https://dgjsxb.ces-transaction.com/EN/10.19595/j.cnki.1000-6753.tces.200304     OR     https://dgjsxb.ces-transaction.com/EN/Y2021/V36/I5/1006
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech