A New Method for Frequency Control Performance Assessment on Operation Security
Chang Yekui, Li Weidong, Ba Yu, Liu Rao, Wang Haixia
College of Electrical Engineering Dalian University of Technology Dalian 116024 China

Download: PDF (31301 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  The “Period-Control Performance Standard (P-CPS)”, which is currently applied to assess area’s performance on frequency control in China power grid, has some defects, such as having overly strict requirements for control and being indefensible in index design. This case leads to frequent regulation of units and the inconsistency between assessment result and control performance. Based on the rules of “Technical Guide for Electric Power System Security and Stability Control”, this paper draws out the requirements for frequency control from an operation security perspective. Frequency should have a safety martin in the case of non-contingency and duration for over-limit frequency should be constricted in the case of I level contingency. According to the requirements, a new frequency security assessment method (FSAM) is proposed to monitor and assess areas’ control actions in the cases of non-contingency and I level contingency. The test results show that, with the new method, frequency fluctuates within the defined secure range and operation security can be maintained appropriately. In addition, the number of orders to regulate automatic generation control (AGC) units is decreased, which is beneficial for economical operation.
Key wordsFrequency control      active power balance      automatic generation control (AGC)      operation security      control performance assessment     
Received: 12 February 2018      Published: 29 March 2019
PACS: TM73  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Chang Yekui
Li Weidong
Ba Yu
Liu Rao
Wang Haixia
Cite this article:   
Chang Yekui,Li Weidong,Ba Yu等. A New Method for Frequency Control Performance Assessment on Operation Security[J]. Transactions of China Electrotechnical Society, 2019, 34(6): 1218-1229.
URL:  
https://dgjsxb.ces-transaction.com/EN/10.19595/j.cnki.1000-6753.tces.180240     OR     https://dgjsxb.ces-transaction.com/EN/Y2019/V34/I6/1218
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech