电工技术学报  2016, Vol. 31 Issue (10): 119-126    DOI:
电气设备绝缘状态监测与故障诊断专题 |
一种多样本信息的局部放电源逐次逼近定位方法
唐炬1,2, 黄亮2,3, 曾福平1, 张晓星1,2
1. 武汉大学电气工程学院 武汉 430072;
2. 输配电装备及系统安全与新技术国家重点实验室(重庆大学) 重庆 400044;
3. 国网重庆市电力公司永川供电分公司 重庆 402160
A Positioning Approach Based on Successive Approximation of Multi-Samples for Partial Discharge Source
Tang Ju1,2, Huang Liang2,3, Zeng Fuping1, Zhang Xiaoxing1,2
1. School of Electrical Engineering Wuhan University Wuhan 430072 China;
2. State Key Laboratory of Power Transmission Equipment & System Security and New Technology Chongqing University Chongqing 400044 China;
3. State Grid Chongqing Yongchuan Power Supply Company Chongqing 402160 China
全文: PDF (329 KB)  
输出: BibTeX | EndNote (RIS)      
摘要 时延估计是利用时间差方法对局部放电(PD)源准确定位的关键,然而在测量时延时不可避免地产生误差,从而导致因时延获取准确度不高而带来定位误差大的问题。因此,为了降低时间差定位法中对准确获取时延的依赖性,提出一种基于多样本寻优PD源的逐次逼近定位方法。采用逐次逼近式粒子群搜索原理,对传统定位方法得到的单样本初值与传感器阵列所建立的寻优目标函数进行递归逼近处理,最终确定最优PD源位置。通过对实验室实测PD信号逐次逼近寻优定位,表明提出的逐次逼近定位方法可有效地解决因时间差测量不准确而引起的定位结果较差的难题,结果较传统时间差定位方法具有更高的准确度,验证了所提方法的正确性与有效性。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
唐炬
黄亮
曾福平
张晓星
关键词 局部放电 到达时间差 逐次逼近方法 粒子群优化 定位准确度    
Abstract:Time-delay estimation is the key to locate partial discharge (PD) source accurately with the time difference of arrival (TDOA) method. However, the time-delay error inevitably exists during measuring time difference, which leads to large location error because of low time delay accuracy. In order to reduce the dependency of the TDOA method on time delay accuracy, a novel PD source location approach based on successive approximation of multi-samples is proposed in this paper. The particle swarm optimization is employed to recurrently perform the optimization objective function. In this optimization objective function, the single sample value is obtained by the traditional TDOA method, while sensor array in turn determines the optimal location of the PD source. Experimental results show that the proposed method can effectively solve the problem of low location accuracy for the PD source caused by the poor accuracy of time delay measurements. The positioning result of the proposed method is potentially better than that of the traditional TDOA method, which verifies the proposed method.
Key wordsPartial discharge    time difference of arrival    successive approximation method    particle swarm optimization    positioning accuracy   
收稿日期: 2015-05-23      出版日期: 2016-07-11
PACS: TM835  
基金资助:国家自然科学基金(51377181)和重庆市基础与前沿研究计划(cstc2013jjb90002)资助项目
通讯作者: 唐 炬 男,1960年生,教授,博士生导师,研究方向为电气设备绝缘状态在线监测与故障诊断技术、高电压测试技术等。E-mail: cqtangju@vip.sina.com(通信作者)   
作者简介: 黄 亮 男,1984年生,博士研究生,研究方向为电气设备绝缘装备在线监测与故障诊断技术。E-mail: huangliang112@gmail.com
引用本文:   
唐炬, 黄亮, 曾福平, 张晓星. 一种多样本信息的局部放电源逐次逼近定位方法[J]. 电工技术学报, 2016, 31(10): 119-126. Tang Ju, Huang Liang, Zeng Fuping, Zhang Xiaoxing. A Positioning Approach Based on Successive Approximation of Multi-Samples for Partial Discharge Source. Transactions of China Electrotechnical Society, 2016, 31(10): 119-126.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/Y2016/V31/I10/119