Abstract:In the synchronous rotating frame,coupling exists in the mathematical model of the grid-connected inverters adopting LCL filters.And serious distortion occurs in the inverter output current under unbalanced grid voltage or with low order harmonics in the grid voltage.Considering problems mentioned above,this paper presents a current repetitive control strategy in the stationary frame.The proposed method does not require the Park transformation or the decoupling process.It is able to effectively reduce the total harmonic distortion of the injected grid current.The specific design method of the repetitive controller is provided,considering the hardware parameters of the LCL filter and the influence of the system delay.Simulation and experimental results are presented in the end,which verifies the validity of the theoretical analysis and the effectiveness of the proposed method.
[1] IEEE519—1992.Recommended practices and requirements for harmonic control in electrical power systems[S]. [2] 刘飞,查晓明,段善旭.三相并网逆变器LCL滤波器的参数设计与研究[J].电工技术学报,2010,25(3):110-116. Liu Fei,Zha Xiaoming,Duan Shanxu.Design and research on parameter of LCL filter in three-phase grid-connected inverter[J].Transactions of China Electrotechnical Society,2010,25(3):110-116. [3] 彭双剑,罗安,荣飞,等.LCL滤波器的单相光伏并网控制策略[J].中国电机工程学报,2011,31(21):17-124. Peng Shuangjian,Luo An,Rong Fei,et al.Single-phase photovoltaic grid-connected control strategy with LCL filter[J].Proceedings of the CSEE,2011,31(21):17-124. [4] Teodorescu R,Blaabjerg F,Borup U,et al.A new control structure for grid-connected LCL PV inverters with zero steady-state error and selective harmonic compensation[C]//Nineteenth Annual IEEE Applied Power Electronics Conference and Exposition,Anaheim,California,2004,1:580-586. [5] 李玉玲,鲍建宇,张仲超.间接电流控制可调功率因数电流型PWM变流器[J].中国电机工程学报,2007,27(1):49-53. Li Yuling,Bao Jianyu,Zhang Zhongchao.Indirect current control adjustable power factor current source pwm converter[J].Proceedings of the CSEE,2007,27(1):49-53. [6] 王斯然,吕征宇.锂电池馈电并网系统进网电流谐波抑制方法[J].电工技术学报,2009,33(19):90-95. Wang Siran,Lü Zhengyu.A harmonics suppression method for lithium battery grid integration system[J].Transactions of China Electrotechnical Society,2009,33(19):90-95. [7] Twining E,Holmes D G.Grid current regulation of a three-phase voltage source inverter with an LCL input filter[J].IEEE Transactions on Power Electronics,2003,18(5):888-895. [8] Yang Shuitao,Lei Qin,Peng Fangzheng,et al.A robust control scheme for grid-connected voltage-source inverters[J].IEEE Transactions on Industrial Electronics,2012,58(1):202-212. [9] 张凯,鹏力,熊健,等.基于状态反馈与重复控制的逆变器控制技术[J].中国电机工程学报,2006,26(10):56-62. Zhang Kai,Peng Li,Xiong Jian,et al.State-feedback-with-integral control plus repetitive control for PWM inverters[J].Proceedings of the CSEE,2006,26(10):56-62. [10]Chen D,Zhang J,Qian Z.An improved repetitive control scheme for grid-connected inverter with frequency-adaptive capability[J].IEEE Transactions on Industrial Electronics,2013,60(2):814-823. [11]王斯然,吕征宇.LCL型并网逆变器中重复控制方法研究[J].中国电机工程学报,2010,30(27):69-75. Wang Siran,Lü Zhengyu.Research on repetitive control method applied to grid-connected inverter with LCL filter[J].Proceedings of the CSEE,2010,30(27):69-75.