Development Rules of Accelerated Degradation of Oil-Paper Insulation between Turns in Transformer Windings Induced by Partial Discharge
Cheng Yangchun1, Wei Jinqing1, Li Chengrong2, Rong Zhihai1, Wang Guangzhen1, Ma Zhenli1
1. Beijing Key Laboratory of High Voltage and Electromagnetic Compatibility North China Electric Power University Beijing 102206 China; 2. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources North China Electric Power University Beijing 102206 China
Abstract:Tests based on the inter-turn partial discharge model are conducted to study the development rules of oil-paper insulation material defects generated by partial discharge in power transformers and its possible correlation with the characteristics of partial discharge. The constant voltage is adopted in this series of tests. High voltage is applied on the inter-turn electrode specimens with different time length in different groups of tests. Real-time detection is conducted to record conventional impulse current signals from partial discharge. After tests, insulation tapes were stripped from inter-turn electrodes lay by layer. In this way, the statistical laws about the development rules of the carbon channels generated by accelerated degradation between turns are acquired. The results show that the development of the carbon channels generated by accelerated degradation under a high constant voltage can be divided into three basic stages: growth, stagnation, and breakdown. The pulse repetition rate and the summation of pulse amplitude per second can reflect the insulate degradation development state of the inter-turn oil paper system. Based on these results, the severity of partial discharge in the oil-paper insulation can be assessed accurately.
程养春, 魏金清, 李成榕, 荣智海, 王广真, 马振丽. 局部放电作用下变压器匝间油纸绝缘加速劣化规律[J]. 电工技术学报, 2015, 30(18): 203-212.
Cheng Yangchun, Wei Jinqing, Li Chengrong, Rong Zhihai, Wang Guangzhen, Ma Zhenli. Development Rules of Accelerated Degradation of Oil-Paper Insulation between Turns in Transformer Windings Induced by Partial Discharge. Transactions of China Electrotechnical Society, 2015, 30(18): 203-212.
[1] Wang Le, Cavallini A, Montanari G C, et al. Evo- lution of PD patterns in polyethylene insulation cavities under AC voltage[J]. IEEE Transaction on Dielectrics and Electrical Insulation, 2012, 19(2): 533-542. [2] Okamoto T. Novel partial discharge measurement computer-aided measurement systems[J]. IEEE Trans- actions on Dielectrics and Electrical Insulation, 1986, 21(6): 1015-1019. [3] Hikita M. Measurements of partial discharges by computer and analysis of partial discharge distri- bution by the Mote Carlo method[J]. IEEE Trans- action on Dielectrics and Electrical Insulation, 1990, 25(3): 453-468. [4] Dissado L A, Sweeney P. Physical model for break- down structures in solid dielectrics[J]. Physical Review B, 1993, 48(22): 16261-16268. [5] Montanari G C. Aging and life models for insulation systems based on PD detection[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1995, 2(4): 667-675. [6] Bozzo R, Gemme C, Guastavino C, et al. Aging diagnosis of insulation systems by PD measurements extraction of partial discharge features in electrical treeing[J]. IEEE Transaction on Dielectrics and Electrical Insulation, 1998, 5(1): 118-124. [7] Wu Kai, Suzuoki Y, Mizutani T, et al. A novel physical model for partial discharge in narrow channels[J]. IEEE Transaction on Dielectrics and Electrical Insulation, 1999, 6(2): 181-190. [8] 陈向荣, 徐阳, 王猛, 等. 高温下110kV交联聚乙烯电缆电树枝生长及局部放电特性[J]. 高电压技术, 2012, 38(3): 645-654. Chen Xiangrong, Xu Yang, Wang Meng, et al. Pro- pagation and partial discharge characteristics of electrical trees in 110kV XLPE cable insulation at high temper- ature[J]. High Voltage Engineering, 2012, 38(3): 645-654. [9] 郑晓泉, Chen G, Davies A E. 交联聚乙烯电缆绝缘中的双结构电树枝特性及其形态发展规律[J]. 中国电机工程学报, 2006, 26(3): 79-85. Zheng Xiaoquan, Chen G, Davies A E. Characteristic and development law of a double structure electrical tree in XLPE cable insulation[J]. Proceedings of the CSEE, 2006, 26(3): 79-85. [10] 陈小林, 成永红, 谢小军, 等. XLPE绝缘电老化中局放特性试验研究[J]. 高电压技术, 2006, 32(4): 22-24. Chen Xiaolin, Cheng Yonghong, Xie Xiaojun, et al. Experimental study on partial discharge in XLPE insulation during electrical aging[J]. High Voltage Engineering, 2006, 32(4): 22-24. [11] 王洪新, 张水平, 程树康, 等. XLPE电树老化过程中的局放特性[J]. 高电压技术, 2003, 29(6): 19-21. Wang Hongxin, Zhang Shuiping, Cheng Shukang, et al. Study on PD characteristics in the course of electrical tree aging in XLPE[J]. High Voltage Engineering, 2003, 29(6): 19-21. [12] 贺景亮. 交联聚乙烯绝缘中树状放电的试验研究[J]. 中国电机工程学报, 1996, 16(1): 46-49. He Jingliang. An experimental study of electrical treeing in polythylene[J]. Proceedings of the CSEE, 1996, 16(1): 46-49. [13] 常文治, 李成榕, 苏錡, 等. 电缆接头尖刺缺陷局部放电发展过程的研究[J]. 中国电机工程学报, 2013, 33(7): 192-201. Chang Wenzhi, Li Chengrong, Su Qi, et al. Study on development of partial discharges at the defect caused by needle damage to a cable joint[J]. Proceedings of the CSEE, 2013, 33(7): 192-201. [14] Liao Ruijin, Yang Lijun, Li Jian, et al. Aging condition assessment of transformer oil-paper insulation model based on partial discharge analysis[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2011, 18(1): 303-311. [15] 严家明, 廖瑞金, 杨丽君, 等. 局部放电作用下油浸绝缘纸的微观结构及电气性能[J]. 中国电机工程学报, 2011, 31(19): 114-121. Yan Jiaming, Liao Ruijin, Yang Lijun, et al. Microstrure and electrical performance of oil-immersed insulation paper under partial discharge[J]. Proceedings of the CSEE, 2011, 31(19): 114-121. [16] 李军浩, 司文荣, 李彦明, 等. 油纸绝缘内部气隙缺陷电劣化过程中局部放电的测量与模拟[J]. 中国电机工程学报, 2009, 29(31): 128-134. Li Junhao, Si Wenrong, Li Yanming, et al. Measurement and simulation of partial discharge in disc-void of oil-pressboard insulation with electrical degradation process[J]. Proceedings of the CSEE, 2009, 29(31): 128-134. [17] Rudranna N, Rajan J S. Modeling of copper sulphide migration in paper oil insulation of transformers[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2012, 19(5): 1642-1649. [18] Rudranna N, Krishnan V, Rajan J S, et al. Application of FEM for understanding the electric field distribution in copper sulphide contaminated paper-oil insulation of power transformer[C]. Proceedings of the 9th IEEE International Conference on Properties and Applications of Dielectric Materials, Australia, 2009: 73-76. [19] Morshuis. Degradation of solid dielectrics due to internal partial discharge: some throughts on progress made and where to go now[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2005, 12(5): 905-913.