电工技术学报  2025, Vol. 40 Issue (5): 1628-1638    DOI: 10.19595/j.cnki.1000-6753.tces.240274
高电压与放电 |
基于短时分数阶傅里叶变换与时频域反射法的电缆缺陷定位方法
饶显杰1, 徐忠林1, 丁玉琴1, 胡潇予1, 周凯2
1.国网四川省电力公司成都供电公司 成都 610041;
2.四川大学电气工程学院 成都 610065
Cable Defect Localization Method Based on Short-Time Fractional Fourier Transform and Time-Frequency Domain Reflectometry
Rao Xianjie1, Xu Zhonglin1, Ding Yuqin1, Hu Xiaoyu1, Zhou Kai2
1. Chengdu Power Supply Company State Grid Sichuan Power Supply Company Chengdu 610041 China;
2. College of Electrical Engineering Sichuan University Chengdu 610065 China
全文: PDF (3604 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 为解决传统时频域反射法(TFDR)存在的时频分辨率低、交叉项干扰严重等问题,该文提出了一种基于短时分数阶傅里叶变换(STFRFT)与TFDR的电缆缺陷定位方法。首先,建立电力电缆的分布参数模型,研究TFDR参考信号的时频分布特征;然后,根据TFDR参考信号的频率变化系数确定STFRFT的旋转角度,获取入射、反射信号的高分辨率时频分布;最后,通过入射、反射信号的时频互相关函数构建电缆的缺陷定位曲线,该曲线的局部峰值可指示电缆的缺陷位置。多分量参考信号的时频分布结果表明,该方法可以准确地获取入射、反射信号的高分辨率时频分布,并且不存在交叉项干扰。同时,500 m电缆模型与105 m的10 kV电力电缆的缺陷定位结果说明,该方法可以灵敏地定位电缆缺陷,且定位精度较高,相比于传统的正交匹配追踪-伪维格纳分布法、平滑伪维格纳分布法,具备更好的缺陷定位效果。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
饶显杰
徐忠林
丁玉琴
胡潇予
周凯
关键词 电力电缆缺陷定位时频域反射时频分布短时分数阶傅里叶变换    
Abstract:The time-frequency domain reflectometry (TFDR) method is widely used to detect and locate cable defects. However, traditional TFDR methods have problems such as low time-frequency resolution and severe cross-term interference, which make it difficult to accurately locate weak cable defects. To address these issues, this paper proposes a cable defect localization method based on short-time fractional Fourier transform (STFRFT) and TFDR. The STFRFT is used to obtain the high-resolution time-frequency distribution of the incident signal and the reflected signal, which can maintain the compact support of the signal in the time-frequency domain and eliminate cross-term interference.
Firstly, in the distributed parameter model of the power cable, the incident signal of TFDR is the Gaussian envelope linear frequency modulation signal, which can produce the reflected signal with the same time-frequency domain characteristic. So both the incident signal and the reflected signal have compact support in the time-frequency domain. Secondly, the STFRFT has a high resolution for non-stationary signals such as the linear frequency modulation signal, therefore the frequency variation coefficient of the TFDR reference signal is used to determine the rotation angle of STFRFT, which can obtain a high-resolution time-frequency distribution of the incident signal and the reflected signal. Finally, the time-frequency cross-correlation function is established as the cable defect localization curve, and the local peak of the curve shows the location of the cable defect.
The time-frequency distributions of multi-component reference signals show that, the quadratic transformation of the Wigner-Ville distribution (WVD) causes serious cross-term interference, which significantly affects the authenticity of the time-frequency distribution. The Fourier transform of synchronous squeezing transformation (SST) makes it difficult to focus the frequency domain energy of the linear frequency modulation signal, leading to the signal energy dispersion in the time-frequency distribution. The time-varying time-frequency resolution in the S-transform causes signal energy distortion in the time-frequency distribution, which weakens the compact support of the signal in the time-frequency domain. Because the STFRFT can effectively focus the signal energy in the time-frequency domain, the proposed method can accurately obtain a high-resolution time-frequency distribution of the incident signal and the reflected signal, and it can eliminate cross-term interference.
In this paper, the 500 m 10 kV power cable simulation model is established. The defect is located at 300 m, while the defect length is 1 m. Since the defect can change the characteristic impedance of the local area, this paper sets the characteristic impedance of the simulated defect area to 1.05 times that of the normal area. The local peak of the proposed defect localization curve can accurately locate the cable defect with an error of only 0.79 m. In addition, the peak value of the defect is 0.98, which approaches the maximum value 1 of the curve. Meanwhile, there are no false local peaks in the proposed defect localization curve.
In the measurement process, the experimental subject is a 105 m 10 kV XLPE power cable, which has a local corrosion defect caused by water. To suppress the cross-term interference, orthogonal matching pursuit and pseudo Wigner-Ville distribution (OMP-PWVD) need to sacrifice the time-frequency resolution of the reflected signal, while smoothed pseudo Wigner-Ville distribution (SPWVD) need to sacrifice the time-frequency energy of the reflected signal. As a result, the traditional OMP-PWVD and SPWVD make it difficult to locate the local corrosion defect in the power cable. As same as the simulation results, the proposed defect localization curve can accurately locate the defect, in which the positioning error is only 0.99 m.
The conclusions of this article are summarized as follows: (1) In STFRFT, the signal can be converted to the fractional domain by rotation angle θ. Based on the time-frequency characteristics of the TFDR reference signal, the θ is set to arccot[-b/(2π)], which can effectively focus the signal energy and improve signal resolution in the time-frequency domain. (2) Compared with traditional methods, the time-frequency distribution of the STFRFT can keep the compact support of signal in the time-frequency domain and eliminate cross-term interference. (3) The defect localization results of a 500 m cable model and a 105 m 10 kV power cable show that the proposed method can sensitively locate cable defects with a high positioning accuracy. Compared with traditional OMP-PWVD and SPWVD, the method proposed in this paper has a better defect localization result.
Key wordsPower cable    defect location    time-frequency domain reflectometry    time-frequency distribution    short-time fractional Fourier transform   
收稿日期: 2024-02-19     
PACS: TM41  
基金资助:国网四川省电力公司科技项目资助(521904230003)
通讯作者: 周 凯, 男,1975年生,教授,博士生导师,研究方向为电缆绝缘状态检测与修复等。E-mail:zhoukai_scu@163.com   
作者简介: 饶显杰, 男,1996年生,硕士,研究方向为电力设备绝缘状态监测。 E-mail:1953520244@qq.com
引用本文:   
饶显杰, 徐忠林, 丁玉琴, 胡潇予, 周凯. 基于短时分数阶傅里叶变换与时频域反射法的电缆缺陷定位方法[J]. 电工技术学报, 2025, 40(5): 1628-1638. Rao Xianjie, Xu Zhonglin, Ding Yuqin, Hu Xiaoyu, Zhou Kai. Cable Defect Localization Method Based on Short-Time Fractional Fourier Transform and Time-Frequency Domain Reflectometry. Transactions of China Electrotechnical Society, 2025, 40(5): 1628-1638.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.240274          https://dgjsxb.ces-transaction.com/CN/Y2025/V40/I5/1628