Switching Impulse Flashover Characteristics of Live Working Air Gaps in High Altitude Areas and Discharge Voltage Correction
Fang Yaqi1, Wang Linong2, Li Rui3, Liu Kai4, Song Bin2
1. School of Electrical and Electronic Engineering Hubei University of Technology Wuhan 430068 China; 2. School of Electrical Engineering and Automation Wuhan University Wuhan 430072 China; 3. Wuhan Power Supply Company State Grid Hubei Electric Power Co. Ltd Wuhan 430050 China; 4. China Electrical Power Research Institute Wuhan 430074 China
Abstract:Since the air gap discharge voltage in high-altitude areas is significantly lower than that in low-altitude areas, the minimum approach distance required for live working increases. In order to ensure the safety operation of live working in high altitude areas, the switching impulse discharge tests are conducted on 750kV double-circuit tower in areas with altitude of 2 000m, 3 000m and 4 300m, and the discharge characteristics of equipotential worker-tower gap and bundle conductor-ground potential worker gap are obtained. The influences of altitude and worker's posture on the discharge characteristics of live working gaps are analyzed. Based on the test data, the applicability of the m-method recommended by IEC standard is evaluated. The results show that the existing method is not suitable for discharge voltage correction of live working gaps in areas with altitude above 3 000m. Finally, a modified m-method is proposed based on test data, which can be used to correct switching impulse discharge voltage of live working gaps at the altitude of 3 000~4 300m. In addition, the minimum approach distance of live working in areas at the altitude of 2 000~4 000m is determined.
方雅琪, 王力农, 李瑞, 刘凯, 宋斌. 高海拔带电作业间隙操作冲击放电特性及放电电压校正[J]. 电工技术学报, 2020, 35(12): 2681-2688.
Fang Yaqi, Wang Linong, Li Rui, Liu Kai, Song Bin. Switching Impulse Flashover Characteristics of Live Working Air Gaps in High Altitude Areas and Discharge Voltage Correction. Transactions of China Electrotechnical Society, 2020, 35(12): 2681-2688.
[1] 胡毅, 刘凯, 彭勇, 等. 带电作业关键技术研究进展与趋势[J]. 高电压技术, 2014, 40(7): 1921-1931. Hu Yi, Liu Kai, Peng Yong, et al.Research status and development trend of live working key technology[J]. High Voltage Engineering, 2014, 40(7): 1921-1931. [2] Philips T A, Robertson L M, Rohlfs A F, et al. Influence of air density on electrical strength of transmission line insulation[J]. IEEE Transactions on Power Apparatus and Systems, 1967, PAS-86(8): 948-961. [3] Harada T, Aoshiima Y, Ishida Y, et al. Influence of air density on flashover voltage of air gaps and insulators[J]. IEEE Transactions on Power Apparatus and Systems, 1970, PAS-89(6): 1192-1202. [4] Aihara Y, Watanabe Y, Kishizima I.Analysis of new phenomenon regarding effects of humidity on flashover characteristics for long air gaps[J]. IEEE Transactions on Power Apparatus and Systems, 1983, 102(12): 3778-3782. [5] Pigini A, Sartorio G, Moreno M, et al. Influence of air density on the impulse strength of external insulation[J]. IEEE Transactions on Power Apparatus and Systems, 1985, PAS-104(10): 2888-2900. [6] Ramirez M, Pigini A, Rizzi G, et al.Air density influence on the strength of external insulation under positive impulse: experimental investigation up to an altitude of 3000m a. s. l.[J]. IEEE Transactions on Power Delivery, 1990, 5(2): 730-737. [7] Ortéga P, Waters R T, Haddad A, et al.Impulse breakdown voltages of air aaps: a new approach to atmospheric correction factors applicable to international standards[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(6): 1498-1508. [8] Calva P A, Espino F P.Correction factors for positive DC voltages[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 1998, 5(4): 541-544. [9] Ortega P, Waters R T, Haddad A, et al.Impulse breakdown voltages of air gaps: a new approach to atmospheric correction factors applicable to international standards[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2007, 14(6): 1498-1508. [10] 梅忠恕. 空气间隙击穿电压的等值相对空气密度校正法[J]. 高电压技术, 1987, 13(1): 62-67. Mei Zhongshu.Equivalent relative air density correction method for air gap breakdown voltage[J]. High Voltage Engineering, 1987, 13(1): 62-67. [11] 龙玉华. 高海拔地区的空气湿度对操作波放电的影响[J]. 高电压技术, 1994, 20(2): 58-60. Long Yuhua.Influence of humidity on SI disruptive discharge voltage in high altitude areas[J]. High Voltage Engineering, 1994, 20(2): 58-60. [12] 蒋兴良, 王军, 苑吉河, 等. 模拟与自然环境下0.5~1.5m空气间隙正极性操作冲击放电电压校正方法[J]. 中国电机工程学报, 2008, 28(28): 13-17. Jiang Xingliang, Wang Jun, Yuan Jihe, et al.Correction method of positive switching impulse discharge voltage for 0.5~1.5m air gap under artificial and natural conditions[J]. Proceedings of the CSEE, 2008, 28(28): 13-17. [13] 夏喻, 李卫国, 陈艳. 高空下棒-板间隙直流放电特性及电压校正[J].电工技术学报, 2018, 33(9): 2115-2120. Xia Yu, Li Weiguo, Chen Yan.DC discharge performance and voltage correction of air gaps under high altitude[J]. Transaction of China Electrotechnical Society, 2018, 33(9): 2115-2120. [14] 丁玉剑, 李庆峰, 廖蔚明, 等. 高海拔地区典型长空气间隙的操作冲击放电特性和海拔校正[J]. 高电压技术, 2013, 39(6): 1441-1446. Ding Yujian, Li Qingfeng, Liao Weiming, et al.Switching impulse discharge characteristics and altitude corrections for typical long air gaps at high altitude areas[J]. High Voltage Engineering, 2013, 39(6): 1441-1446. [15] 廖永力, 李锐海, 李小建, 等. 典型空气间隙放电电压修正的试验研究[J]. 中国电机工程学报, 2012, 32(28): 171-176. Liao Yongli, Li Ruihai, Li Xiaojian, et al.Experimental research on typical air gap test voltage correction[J]. Proceedings of the CSEE, 2012, 32(28): 171-176. [16] 邓慰, 孟刚, 陈勇, 等. 高海拔地区500kV单回输电线路空气间隙放电特性[J]. 电工技术学报, 2013, 28(9): 255-260. Deng Wei, Meng Gang, Chen Yong, et al.Flashover characteristic for high altitude 500kV single-circuit transmission line[J]. Transaction of China Electrotechnical Society, 2013, 28(9): 255-260. [17] 杨亚奇, 李卫国, 夏喻, 等. 低气压下长间隙交直流放电特性研究[J]. 电工技术学报, 2018, 33(5): 1143-1150. Yang Yaqi, Li Weiguo, Xia Yu, et al.Research of AC and DC discharge characteristics of long gap under low pressure[J]. Transaction of China Electrotechnical Society, 2018, 33(5): 1143-1150. [18] 丁玉剑, 周松松, 范建斌, 等. 基于g参数法的棒-板长空气间隙操作冲击电压海拔校正分析[J]. 中国电机工程学报, 2017, 37(10): 2783-2789. Ding Yujian, Zhou Songsong, Fan Jianbin, et al.Analysis on altitude correction of switching impulse discharge voltage for long rod-plate air gaps based on the g-method[J]. Proceedings of the CSEE, 2017, 37(10): 2783-2789. [19] 丁玉剑, 廖蔚明, 孙昭英, 等. ±1000kV直流输电线路塔头间隙冲击放电特性试验及海拔校正研究[J]. 中国电机工程学报, 2011, 31(34): 156-162. Ding Yujian, Liao Weiming, Sun Zhaoying, et al.Experimental studies on impulse flashover characteristics of tower head air gaps of ±1000kV DC transmission lines and altitude correction methods[J]. Proceedings of the CSEE, 2011, 31(34): 156-162. [20] IEC 60060-1: 2010 High-voltage test techniques, part 1: general definitions and requirements[S]. Geneva: International Electrotechnical Commission, 2010. [21] GB/T 16927B/T 16927.1-2011 高电压试验技术第1部分: 一般定义及试验要求[S]. 北京: 中国标准出版社, 2011. [22] DL/T 620-1997 交流电气装置的过电压保护和绝缘配合[S]L/T 620-1997 交流电气装置的过电压保护和绝缘配合[S]. 北京: 中国电力出版社, 1997. [23] IEC 60071-2: 1996 Insulation co-ordination-part 2: application guidelines[S]. Geneva: International Electrotechnical Commission, 1996. [24] GB 311B 311.1-2012 绝缘配合第1部分: 定义、原则和规则[S]. 北京: 中国标准出版社, 2012. [25] GB/T 16927B/T 16927.2-2013 高电压试验技术第2部分: 测量系统[S]. 北京: 中国标准出版社, 2013. [26] 胡毅, 王力农, 刘凯, 等. 750kV同塔双回输电线路带电作业技术研究[J]. 高电压技术, 2009, 35(2): 373-378. Hu Yi, Wang Linong, Liu Kai, et al.Research of live working on 750kV double circuit AC transmission line[J]. High Voltage Engineering, 2009, 35(2): 373-378. [27] IEC 61472-2013 Live working-Minimum approach distances for a.c. systems in the voltage range 72.5kV to 800kV·A method of calculation[S]. Geneva: International Electrotechnical Commission, 2013.