Influence of Space Charge on Air Gap Discharge Under Switching Impulse
Zhan Huamao1, 2, Liu Bo1, 2, Yan Tingli1, 2, Deng Lihong3, Li Chengrong1, 2
1. Beijing Area Major Laboratory of High Voltage and EMC North China Electric Power University Beijing 102206 China; 2. State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources North China Electric Power University Beijing 102206 China; 3. State Grid AC Engineering Construction Company Beijing 100052 China; 4. Laiwu Electric Power Company Laiwu 271100 China; 5. Institute of Urban Construction Beijing 100120 China
Abstract:Shielding failure is the main reason for tripping operations of EHV and UHV transmission lines, and many scholars believe that space charge may be one of the causes of these shielding failure accidents. In order to further study the influence of space charge on lightning discharge, a board-needle air gap of 100cm was set up. Under the positive and negative switching impulse voltage, the discharge process of the gap was observed by a high speed video camera system. So as to analyze the influence of the space charge on the discharge development quantitatively, the current through the positive board-needle air gap was measured. Then the charge current was extracted, and the integral of the charge current was calculated to evaluate the amount of space charge. Experimental results show that discharge always develops from the positive electrode to the negative electrode, under both positive and negative switching impulse voltage. Besides, under the positive switching impulse voltage, with the radius of curvature of the head part of the needle increasing, the percentage of discharge striking points on the head of the needle decreases. What's more, under the same test conditions, the amount of the space charge of the board-pointed needle is the largest. With the radius of curvature of the head part of the needle increasing, the amount of the space charge becomes smaller.
詹花茂, 刘波, 颜廷利, 邓丽红, 李成榕. 操作冲击下空间电荷对间隙放电的影响[J]. 电工技术学报, 2014, 29(2): 212-218.
Zhan Huamao, Liu Bo, Yan Tingli, Deng Lihong, Li Chengrong. Influence of Space Charge on Air Gap Discharge Under Switching Impulse. Transactions of China Electrotechnical Society, 2014, 29(2): 212-218.
[1] 钱冠军, 王晓瑜, 徐先芝, 等. 输电线路绕击分散性的试验研究[J]. 高电压技术, 1998, 24(3): 17-20. Qian Guanjun, Wang Xiaoyu, Xu Xianzhi, et al. Study of scatter of shielding failure on transmission line[J]. High Voltage Engineering, 1998, 24(3): 17-20. [2] Moore C B, William Rison, James Mathis, et al. Lightning rod improvement studies[J]. Journal of Applied Meteorology, 2000, 39: 593-609. [3] 钱冠军, 王晓瑜, 丁一正, 等. 500kV线路直击雷典型事故调查研究[J]. 高电压技术, 1997, 23(2): 72-74. Qian Guanjun, Wang Xiaoyu, Deng Yizheng. Investigation of typical direct lightning strike accidents on 500kV lines[J]. High Voltage Engin- eering, 1997, 23(2): 72-74. [4] 詹花茂, 邓丽红, 郝丽霞, 等. 正极性电压下空间电荷对空气间隙放电击中点的影响研究[J]. 高电压技术, 2011, 37(9): 2211-2217. Zhan Huamao, Deng Lihong, Hao Lixia, et al. Effect of space charge on striking points of air gap discharge under positive voltages[J]. High Voltage Engineering, 2011, 37(9): 2211-2217. [5] Marley Becerra, Vernon Cooray. A Simplified physical model to determine the lightning upward connecting leader inception[J]. IEEE Transactions on Power Delivery, 2006, 21(2): 897-908. [6] Gallimberti. The mechanism of long spark formation [M]. Italy: Physique Coll, 1972. [7] 廖蔚明, 崔国华, 孙昭英, 等. ±800kV直流线路杆塔塔头空气间隙的直流叠加操作冲击放电特性[J]. 电网技术, 2008, 32(9): 6-9 Liao Weiming, Cui Guohua, Sun Zhaoying, et al. Flashover test on air clearances of ±800 kV DC transmission tower with switching surges superim- posed on DC voltage[J]. Power System Technology, 2008, 32(9): 6-9. [8] 王黎明, 毛苏春, 关志成. 棒-板间隙在交直流预电压作用下的冲击特性[J]. 清华大学学报, 2002, 42(3): 285-287. Wang Liming, Mao Suchun, Guan Zhicheng. Sparkover of rod-plane gap for composite alternating or direct/impulse voltages[J]. Journal of Tsinghua University(Science and Technology), 2002, 42(3): 285-287. [9] 曾嵘, 耿屹楠, 牛犇, 等. 空气间隙放电物理参数测量研究进展[J]. 高电压技术, 2011, 37(3): 528-536. Zeng Rong, Geng Yinan, Niu Ben, et al. Research progress on parameters measurement of air gap discharge[J]. High Voltage Engineering, 2011, 37(3): 528-536. [10] 耿屹楠, 曾嶸, 何金良, 等. “棒板”间隙雷电冲击放电时高压侧预放电电流的测量[J]. 高电压技术, 2011, 37(4): 854-859. Geng Yinan, Zeng Rong, He Jinliang, et al. Pre-breakdown current measurements from high voltage electrode of rod-plane gap under lightning impulse voltage[J]. High Voltage Engineering, 2011, 37(4): 854-859. [11] Liu Q, Wang Z D. Secondary reverse streamer observed in an ester insulating liquid under negative impulse voltage[J]. Journal of Physics D: Applied Physics, 2011, 44(40): 10-18. [12] Lalande P, Bondiou A, Bacchiega G, et al. Observations and modeling of lightning leaders[J]. C. R. Phys, 2002, 3: 1375-1392. [13] Grzybowski S, Mallick S, Disyadej T. Review of lightning performance study on dissipation devices[C]. North American Power Symposium (NAPS), 2009: 1-5. [14] Taylor C D, Grzybowski S. Spice simulation and measurement of emission current from the static dissipator devices at switching impulse[C]. IEEE Southeast Conference, 2006: 48-61. [15] 杨波, 王黎明, 关志成, 等. 交直流预电压下导线-棒间隙的冲击特性[J]. 清华大学学报, 2002, 42, (S1): 49-51. [15] 杨波, 王黎明, 关志成, 等. 交直流预电压下导线-棒间隙的冲击特性[J]. 清华大学学报, 2002, 42, (S1): 49-51. Yang Bo, Wang Liming, Guan Zhicheng, et al. Air breakdown in conductor-rod gap with direct or alternating voltage switching impulses[J]. Journal of Tsinghua University(Science and Technology), 2002, 42, (S1): 49-51. [16] 蒋兴良, 王军, 胡建林, 等. 1m 针-板空气间隙正极性操作冲击放电特性及电压校正[J]. 中国电机工程学报, 2006, 26(16): 137-143. Jiang Xingliang, Wang Jun, Hu Jianlin, et al. Positive polarity switching impulse discharge performance and voltage correction of 1m rod-plane air gap[J]. Proceedings of the CSEE, 2006, 26(16): 137-143. 作者简介:詹花茂 女,1976年生,博士,副教授,主要研究方向气体放电与电力系统过电压。刘波 女,1987年生,硕士研究生,主要研究方向气体放电与电力系统过电压。