Abstract:The final aim of the control system of grid-connected inverter is to track the reference current. So it is needed to predict the reference current according to the previous two or three switching periods. Due to the mismatch of the model inductance and actual inductance, the impact had on the stability of system for different control algorithms will be different, namely on the premise that the system be stable, different algorithm differs in the tolerance of inductance mismatch. On the basis of analyzing stability of single phase grid-connected inverter control system, advantages and disadvantages of each kind of predictive current control algorithms were compared. The fundamental reason why the control effects differed from each other was indicated. And an improved predictive current control algorithm was proposed that changes the aim of current error from the current difference of previous two periods to a specified one. The proximate calculation of intermediate variable is decreased and the stability of algorithm is improved. The tolerance of inductance dismatch is largely raised. Better stability margin is achieved relative to conventional methods. In the end the superiority is testified through simulation model and experimental platform.
[1] 洪峰, 单任仲, 王慧贞, 等. 一种变环宽准恒频电流滞环控制方法[J]. 电工技术学报, 2009, 24(1): 115-119. [2] 顾和荣, 杨子龙, 邬伟扬. 并网逆变器输出电流滞环跟踪控制技术研究[J]. 中国电机工程学报, 2006, 26(9): 108-112. [3] 郑诗程. 光伏发电系统及其控制的研究[D]. 合肥: 合肥工业大学, 2004. [4] Holtz J. Pulsewidth modulation-a survey[J]. IEEE Transactions on Industry Electronics, 1992, 39(5): 410-420. [5] Jeong S J, Kim B W, Song S H. Improvement of predictive current control performance using on-line parameter estimation in phase controlled rectifier[J]. IEEE Transactions on Power Electronics, 2007, 22(5): 1820-1825. [6] Kojabadi H M, Idris B Y, Gadoura A. A novel DSP-based current-controlled PWM strategy for single phase grid connected inverters[J]. IEEE Transactions on Power Electronics, 2006, 21(4): 985-993. [7] Holtz J, Stadtfeld S. A predictive controller for the stator current vector of AC machines fed from a switched voltage source[C]. Proc. Annu. Meeting Int. Power Electron. Conf., 1983: 1665-1675. [8] 吴理博. 光伏并网逆变系统综合控制策略研究及实现[D]. 北京: 清华大学, 2006. [9] Holmes D G, Martin D A. Implementation of a direct digital predictive current controller for single and three phase voltage source inverter [C]. Proc. Annu. Meeting IEEE, 1996: 906-913. [10] Bode G H, Loh P C, Newman M J, et al. An improved robust predictive current regulation algorithm [J]. IEEE Transactions on Industry Applications, 2005, 41(6): 1720-1733. [11] Malesani L, et al. Robust dead-beat current control for PWM rectifiers and active filters[J]. IEEE Transactions on Industry Applications, 1999, 35(3): 613-620. [12] Rodriguez J, et al. Predictive current control of a voltage source inverter[J]. IEEE Transactions on Industry Electronics, 2007, 54(1): 495-503. [13] Athalye P, Maksimovie D, Erickson R. Variable- frequency predictive digital current mode control[J]. IEEE Power Electronics Letters, 2004, 2(4): 113-116.