Transactions of China Electrotechnical Society  2020, Vol. 35 Issue (7): 1521-1528    DOI: 10.19595/j.cnki.1000-6753.tces.191178
Current Issue| Next Issue| Archive| Adv Search |
Measuring Method of Capacitance to Ground in Resonant Grounding System Based on Transient Information after Arc Extinguishing
Xue Yongduan1, Li Guang1, Xu Bingyin2
1. College of New Energy China University of Petroleum (East China) Qingdao 266580 China;
2. College of Electronics and Electrical Engineering Shandong University of Technology Zibo 255000 China

Download: PDF (1266 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  Accurate measurement of capacitance to ground of the system involves a series of problems such as capacity allocation of arc suppression coil, compensation adjustment, control of residual current at fault point, etc. By using the equivalent circuit of single-phase grounding fault in resonant grounding system, the electrical characteristics of the fault point after arc extinguishing are analyzed. It is found that the transient process after arc extinguishing is the underdamped series resonance process between the inductance of arc suppression coil and the capacitance to ground. The system detuning degree can be calculated by the parameters of resonance frequency and damping factor. Then the capacitance or capacitance current of the system can be calculated according to compensation inductance, which includes zero-sequence inductance of arc suppression coil and grounding transformer. The error of this method is related to the error of resonance frequency, damping factor and compensation inductance. But it mainly depends on the error of compensation inductance. The validity and accuracy of the method are verified by simulation and field data. As a passive measurement method, this method needs no special equipment or adjustment of the operation status of existing equipment, it has high security and provides a new idea for capacitive current measurement of resonant grounding system.
Key wordsResonant grounding system      capacitance current measurement      arc extinguishing      transient      detuning degree     
Received: 17 September 2019      Published: 07 April 2020
PACS: TM930.1  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Xue Yongduan
Li Guang
Xu Bingyin
Cite this article:   
Xue Yongduan,Li Guang,Xu Bingyin. Measuring Method of Capacitance to Ground in Resonant Grounding System Based on Transient Information after Arc Extinguishing[J]. Transactions of China Electrotechnical Society, 2020, 35(7): 1521-1528.
URL:  
https://dgjsxb.ces-transaction.com/EN/10.19595/j.cnki.1000-6753.tces.191178     OR     https://dgjsxb.ces-transaction.com/EN/Y2020/V35/I7/1521
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech