Abstract  The vacuum arc current commutation characteristic plays an important role on breaking process of the low voltage DC hybrid circuit breaker (HCB). In order to gain the current commutation characteristic and the criteria, the structure and principle of the DC HCB is analyzed and the simplified circuit of the current commutation is proposed. The test circuit of the vacuum arc current commutation is set up. The vacuum arc development is observed by the high speed CMOS camera and the influence of the main current, commutation circuit parameters and arcing time on the current commutation is investigated. Based on the test results, the vacuum arc current commutation characteristic and criteria is obtained and the modified criteria are conducted. The breaking test of the 400V/5kA DC HCB is conducted, which also verifies the effectiveness of the criteria. The paper provides the reference of the high performance DC HCB.
Key wordsLow voltage DC hybrid circuit breaker      current commutation characteristic      vacuum arc      commutation criteria     
Received: 02 July 2018      Published: 12 October 2019
PACS: TM561.2  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Ge Guowei
Cheng Xian
Wang Huaqing
Xie Wei
Huang Jinqiang
Cite this article:   
Ge Guowei,Cheng Xian,Wang Huaqing等. Investigation on the Vacuum Arc Current Commutation Criteria of the Low Voltage DC Hybrid Circuit Breaker[J]. Transactions of China Electrotechnical Society, 2019, 34(19): 4038-4047.
URL:  
https://dgjsxb.ces-transaction.com/EN/10.19595/j.cnki.1000-6753.tces.180751     OR     https://dgjsxb.ces-transaction.com/EN/Y2019/V34/I19/4038
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech