Three-Phase Short Circuit Current Characteristic Analysis of Doubly Fed Induction Generator Considering Crowbar Protection Action Time
Fan Xiaohong, An Dechao, Sun Shiyun, Sun Dejuan, Wang Yang
Faculty of Electric Power Engineering Kunming University of Science and Technology Kunming 650500 China

Download: PDF (21775 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  At present, the research on short-circuit current characteristics of DFIG considering Crowbar protection generally assumes that Crowbar protection acts at the moment of fault. In fact, the Crowbar protection does not act instantaneously at the moment of fault because of the control system, but has a certain delay. In view of this practical problem, this paper divides the fault process into two stages, adopts the rotor flux linkage as a bridge between the two stages, and takes the last value of the first stage rotor flux linkage as the initial value of the second stage rotor flux linkage. In addition, the frequency components of stator and rotor flux linkage before and after fault are analyzed, and the analytical expressions of rotor flux linkage are deduced by Laplace and inverse Laplace transformations. Finally, the electromagnetic transient simulation model of DFIG is established on Matlab/Simulink platform. The simulation results verify the correctness of the expression of short-circuit full current of DFIG, and the effect of Crowbar protection action time on short-circuit current is also analyzed.
Key wordsDoubly fed induction generator      Crowbar protection      action time      rotor flux linkage      short-circuit current     
Received: 03 June 2018      Published: 02 September 2019
PACS: TM74  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Fan Xiaohong
An Dechao
Sun Shiyun
Sun Dejuan
Wang Yang
Cite this article:   
Fan Xiaohong,An Dechao,Sun Shiyun等. Three-Phase Short Circuit Current Characteristic Analysis of Doubly Fed Induction Generator Considering Crowbar Protection Action Time[J]. Transactions of China Electrotechnical Society, 2019, 34(16): 3444-3452.
URL:  
https://dgjsxb.ces-transaction.com/EN/10.19595/j.cnki.1000-6753.tces.180957     OR     https://dgjsxb.ces-transaction.com/EN/Y2019/V34/I16/3444
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech