Abstract:The magnitude and composition of transformers no-load current harmonics can be used to examine the saturation degree and detect the inter-turn faults. Generally, a large capacity of industrial-frequency (IF) power supply is used to measure the no-load current harmonics content in transformer factory test. In order to reduce the capacity of testing power supply, this paper proposed a method using low frequency power supply to replace IF power supply to measure no-load current harmonics of transformers. Two low-frequency voltages were first applied to obtain the eddy current and no-load current harmonics. The converted current harmonics content and total harmonics distortion (THDi) under IF were then calculated based on eddy current compensation. In addition, the experiments and simulations were conducted on a single-phase power transformer. Compared with the conversion results of 15Hz, the errors of harmonics content and THDi directly measured under IF are both below 1%. It is shown that this method has high conversion accuracy and can significantly reduce the capacity of testing power supply.
姚陈果, 刘鑫, 胡迪, 万佳伦, 王俊凯. 变压器空载电流谐波低频测量方法[J]. 电工技术学报, 2017, 32(22): 115-21.
Yao Chenguo, Liu Xin, Hu Di, Wan Jialun, Wang Junkai. No-Load Current Harmonics Measurement of Transformers Using Low-Frequency Method. Transactions of China Electrotechnical Society, 2017, 32(22): 115-21.
[1] JB/T 501—2006 电力变压器试验验导则[S]. 2006. [2] 霍崇业, 陈中明. 单相电力变压器空载电流谐波研究[J]. 变压器, 1996, 3(1): 2-6. Huo Chongye, Chen Zhongming. Study of no-load current harmonics of single-phase transformers[J]. Transformer, 1996, 3(1): 2-6. [3] 张国兵. 变压器空载电流谐波测量分析[J]. 变压器, 1997, 34(1): 30-33. Zhang Guobing. Analysis of transformers no-load current harmonics measurement[J]. Transformer, 1997, 34(1): 30-33. [4] Al-Haj A H, El-Amin I. Factors that influence transformer no-load current harmonics[J]. IEEE Transa- ctions on Power Delivery, 2000, 25(1): 163-166. [5] 李钷, 张怡茹. 基于输入观测器理论的电流谐波检测方法[J]. 电工技术学报, 2016, 31(7): 136-143. Li Po, Zhang Yiru. A current harmonics detection method based on input observer theory[J]. Transac- tions of China Electrotechnical Society, 2016, 31(7): 136-143. [6] 黄银龙, 乐健, 毛涛, 等. 一种新型的高压直流输电系统直流侧谐波电压测量方法[J]. 电工技术学报, 2015, 30(22): 144-152. Huang Yinlong, Le Jian, Mao Tao, et al. A novel measurement method of the harmonic voltage on the DC-side of HVDC transmission system[J]. Transac- tions of China Electrotechnical Society, 2015, 30(22): 144-152. [7] Venikar P A, Ballal M S, Umre B S, et al. Transformer incipient inter-turn fault detection based on no-load current harmonic analysis[C]//IEEE Power Tech, Eindhoven, 2015: 1-5. [8] Chowdhury A H, Grady W M, Fuchs E F. An investigation of the harmonic characteristics of transformer excitation current under nonsinusoidal supply voltage[J]. IEEE Transactions on Power Deli- very, 1999, 14(2): 450-458. [9] Siti R M, Hasan S, Anuar M N K. Study the harmonic characteristics of DC bias on the single phase power transformer[C]//IEEE International Power Engin- eering and Optimization Conference, Melaka, 2012: 501-504. [10] 魏玥, 刘天琪, 晏小彬, 等. 高压直流输电系统直流偏磁下的谐波不稳定判据研究[J]. 电力系统保护与控制, 2014, 42(17): 139-144. Wei Yue, Liu Tianqi, Yan Xiaobin, et al. Study of harmonic instability criterion under DC magnetic bias in HVDC system[J]. Power System Protection and Control, 2014, 42(17): 139-144. [11] 赵小军, 崔灿, 李琳, 等. 基于定点谐波平衡法的铁心磁滞与损耗特性分析[J]. 电工技术学报, 2014, 24(5): 46-51. Zhao Xiaojun, Cui Can, Li Lin, et al. Analysis of the hysteresis and loss characteristic in the laminated core by fixed-point harmonic-balanced method[J]. Transactions of China Electrotechnical Society, 2014, 2014, 24(5): 46-51. [12] 王振浩, 王学斌, 李国庆, 等. 计及直流偏磁的保护用电流互感器仿真与实验分析[J]. 电力系统保护与控制, 2015, 43(13): 15-22. Wang Zhenhao, Wang Xuebin, Li Guoqing, et al. Analysis of simulation and experiment on the characteristic of the current transformer used for protection affected by DC magnetic bias[J]. Power System Protection and Control, 2015, 43(13): 15-22. [13] Digalovski M, Najdenkoski K, Rafajlovski G. Impact of current high order harmonic to core losses of three-phase distribution transformer[C]//IEEE Eurocon, Zagreb, 2013: 1531-1535. [14] 王玲, 冯宇, 邱进, 等. 电压互感器谐波特性测量用可控谐波电压源的构建[J]. 电力系统保护与控制, 2015, 43(16): 106-111. Wang Ling, Feng Yu, Qiu Jin, et al. Construction of controllable harmonic voltage source for harmonic characteristic measurement[J]. Power System Pro- tection and Control, 2015, 43(16): 106-111. [15] León F D, Farazmand A, Jazebi S, et al. Elimination of residual flux in transformers by the application of an alternating polarity DC voltage source[J]. IEEE Transactions on Power Delivery, 2015, 30(4): 1727- 1734. [16] 汤蕴璆. 电机学[M]. 北京: 机械工业出版社, 2011. [17] Steinmetz C P. On the law of hysteresis[J]. IEEE Proceeding, 1984, 72(2): 196-221. [18] GB 1094.1—2013 电力变压器 第一部分: 总则[S]. 2013.