Abstract:This paper presents power flow of the double conversion transformerless UPS. The inverter has to supplying average power and oscillating power if the load is unbalanced according to instantaneous power theory. In this paper, the rectifier provides the average power and the DC-bus capacitor provides the oscillating power for the aim of power balance. However, the oscillating DC-bus voltage will lead to input currents coupling with low order harmonic. Therefore, a moving average algorithm is adopted to attenuating the oscillating component, which has a considerable impact on rectifier. This paper presents a dual-loop control scheme for three-phase four-leg PWM rectifier in UPS based on abccoordinate. This control method could effectively attenuate the impact on rectifier which is caused by the current in common leg. Thus, if one of inputs is failed, the others can be operating properly. The simulation and experimental results are in close agreement with the theoretical predictions.
雷何, 肖恩, 林新春, 康勇. UPS前置四桥臂PWM整流器控制策略[J]. 电工技术学报, 2013, 28(1): 203-208.
Lei He, Xiao En, Lin Xinchun, Kang Yong. Control Scheme for Front-End Four-Leg PMW Rectifier in UPS. Transactions of China Electrotechnical Society, 2013, 28(1): 203-208.
[1] Kim G T, Lipo T A. VSI-PWM rectifier/inverter system with a reduced switch count[J]. IEEE Transactions on Industry Applications, 1996, 32(6): 1331-1337. [2] Hiti S, Boroyevich D. Control of front-end three- phase boost rectifier[C]. Proceedings of IEEE Applied Power Electronics Conference and Exposition, 1994. [3] Hiti S, Borojevic D, Ambatipudi R, et al. Average current control of three-phase PWM boost rectifier[C]. Proceedings of IEEE Power Electronics Specialists Conference, 1995. [4] Mao H C, Lee C Y, Boroyevich D, et al. Review of high-performance three-phase power-factor correction circuits[J]. IEEE Transactions on Industrial Electronics, 1997, 44(4): 437-446. [5] Xiong J, Kang Y, Duan S X, et al. Simplified control circuit of three phase PWM rectifier[C]. Proceedings of IEEE Applied Power Electronics Conference and Exposition, 1999. [6] 熊健, 张凯, 陈坚. PWM整流器的控制器工程化设计方法[J]. 电工电能新技术, 2002, 21(3): 44-48. Xiong Jian, Zhang Kai, Chen Jian. An engineering design technique of controller for PWM rectifier[J]. Advanced Technology of Electrical Engineering and Energy, 2002, 21(3): 44-48. [7] Verdelho P, Marques G D. Four-wire current- regulated PWM voltage converter[J]. IEEE Transactions on Industrial Electronics, 1998, 45(5): 761-770. [8] Zhang R, Lee F C, Boroyevich D. Four-legged three- phase PFC rectifier with fault tolerant capability[C]. Proceedings of IEEE Power Electronics Specialists Conference, 2000. [9] Zhang R, Prasad V H, Boroyevich D, et al. Three- dimensional space vector modulation for four-leg voltage-source converters[J]. IEEE Transactions on Power Electronics, 2002, 17(3): 314-326. [10] Tracy J G, Pfitzer H E. Achieving high efficiency in a double conversion transformerless UPS[C]. Proceedings of IEEE Industrial Electronics Society Conference, 2005. [11] Akagi H, Kanazawa Y, Nabae A. Instantaneous reactive power compensators comprising switching devices without energy storage components[J]. IEEE Transactions on Industry Applications, 1984, 20(3): 625-630. [12] Akagi H, Ogasawara S, Hyosung K. The theory of instantaneous power in three-phase four-wire systems a comprehensive approach[C]. Proceedings of IEEE Industry Applications Conference, 1999. [13] Depenbrok M, Staudt V, Wrede H. A theoretical investigation of original and modified instantaneous power theory applied to four-wire systems[J]. IEEE Transactions on Industry Applications, 2003, 39(4): 1160-1168. [14] Kim J H, Sul S K. A carrier-based PWM method for three-phase four-leg voltage source converters[J]. IEEE Transactions on Power Electronics, 2004, 19(1): 66-75.