电工技术学报  2023, Vol. 38 Issue (9): 2418-2434    DOI: 10.19595/j.cnki.1000-6753.tces.220028
电力系统与综合能源 |
基于反向行波幅值比的对称单极柔性直流系统行波方向保护
李晔1, 李斌2, 刘晓明1, 何佳伟2, 贾冠龙1
1.省部共建电工装备可靠性与智能化国家重点实验室 河北工业大学电气工程学院 天津 300132;
2.天津大学智能电网教育部重点实验室 天津大学电气自动化与信息工程学院 天津 300072
The Direction Protection Based on the Amplitude Ratio of the Backward Traveling Wave for the Symmetrical Monopole Flexible DC System
Li Ye1, Li Bin2, Liu Xiaoming1, He Jiawei2, Jia Guanlong1
1. State Key Laboratory of Reliability and Intelligence of Electrical Equipment School of Electrical Engineering Hebei University of Technology Tianjin 300132 China;
2. Key Laboratory of Smart Grid of Ministry of Education School of Electrical and Information Engineering Tianjin University Tianjin 300072 China
全文: PDF (1783 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 快速可靠的方向保护对直流线路保护研究具有重要意义。传统行波方向保护基于正反向行波幅值比识别故障方向,保护动作速度快且无需依赖线路边界,应用前景广阔。但研究发现,当对称单极运行的模块化多电平换流器柔性直流系统发生单极故障时,由于换流站各桥臂子模块投入数量的动态变化会导致直流侧等值阻抗不断变化,从而导致以行波反射系数为整定依据的传统行波方向保护失效。为此,该文提出不依赖线路边界且不受换流站控制响应影响的行波方向保护原理。首先,利用换流站直流出口直流电抗器两侧暂态电压幅值比识别故障是否发生于直流线路侧;然后,利用各条线路反向行波幅值比确定故障线路,有效地消除了换流站控制响应的影响;最后,通过大量的仿真算例充分验证了该文所提方向保护的优势和可行性。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
李晔
李斌
刘晓明
何佳伟
贾冠龙
关键词 柔性直流系统对称单极运行故障行波特性行波方向保护故障方向识别    
Abstract:The flexible DC grid is considered as an important trend of the power system development in the future, with the advantages in large-scale renewable energy access, new urban power supply and so on. However, the DC fault propagation speed of the flexible DC grid is faster, which will damage the whole system in a few milliseconds. Therefore, the fast and reliable direction protection is of great significance for DC line protection. The traditional direction protection based on the amplitude ratio of the forward and backward traveling wave can identify the fault direction fast independent of the line boundary, which has a wide application prospect. However, for the symmetrical monopole flexible DC system, the traditional direction protection cannot identify the pole-to-ground fault direction, because the equivalent impedance of the converter is changing as the result of the dynamic change of the input quantity of the sub-modules. Therefore, a novel direction protection based on the traveling wave is proposed, which is independent of the line boundary and not affected by the converter control influence.
Firstly, the basic principle of the traditional direction protection based on the ratio of the forward traveling wave and the backward traveling wave is introduced. And on this basis, the applicability in the symmetrical monopole flexible DC system is analyzed. For the symmetrical monopole flexible DC system, when the DC pole-to-ground fault occurs, the control response of the converter station will affect the DC fault characteristics, generating the additional fault traveling waves which cannot be accurately calculated. In this case, the traditional traveling wave based direction protection criterion cannot identify the forward and backward faults explicitly in the symmetrical monopole flexible DC system. According to the analysis of fault traveling wave propagation process, there is no backward traveling wave when the backward fault occurs. Therefore, the direction criterion based on the ratio of the backward traveling wave amplitude of each line is proposed. And the proposed direction criterion need not depend on the line boundary elements and is not affected by the nonlinear control of converter. On this basis, the direction protection scheme for the symmetrical monopole flexible DC system is proposed. In the proposed direction protection scheme, the ratio of transient voltage amplitude on both sides of DC reactor is firstly used to identify whether the fault occurs at DC lines, and then the ratio of backward traveling wave amplitude of each line is used to determine the fault line. Finally, a large number of simulation cases are carried out to verify the feasibility and superiority of the proposed direction protection.
The conclusions can be drawn as follows: For the flexible DC system, there is no backward traveling wave at the initial stage of the fault when the backward fault occurs. But when the forward fault occurs, the amplitude of the backward traveling wave is large. Based on this characteristic, a new direction protection principle based on the amplitude ratio of the backward traveling wave of adjacent lines is proposed in this paper. Compared with the traditional traveling wave based direction protection, the performance of the proposed protection is not affected by the dynamic switching process of converter station sub-module after the fault, and the reliability and sensitivity are greatly improved.
Key wordsThe flexible DC system    symmetrical monopolar operation    the characteristics of the fault traveling wave    the traveling wave based direction protection    fault direction identification   
收稿日期: 2022-01-06     
PACS: TM77  
基金资助:国家杰出青年科学基金(52025071)和国家自然科学基金联合基金(U1866205)资助项目。
通讯作者: 李 斌 男,1976年生,教授,博士生导师,研究方向为电力系统保护与控制、柔性直流电网控制保护。E-mail:binli@tju.edu.cn   
作者简介: 李 晔 女,1993年生,博士,讲师,研究方向为柔性直流输配电网故障分析与继电保护。E-mail:liye@hebut.edu.cn
引用本文:   
李晔, 李斌, 刘晓明, 何佳伟, 贾冠龙. 基于反向行波幅值比的对称单极柔性直流系统行波方向保护[J]. 电工技术学报, 2023, 38(9): 2418-2434. Li Ye, Li Bin, Liu Xiaoming, He Jiawei, Jia Guanlong. The Direction Protection Based on the Amplitude Ratio of the Backward Traveling Wave for the Symmetrical Monopole Flexible DC System. Transactions of China Electrotechnical Society, 2023, 38(9): 2418-2434.