电工技术学报  2018, Vol. 33 Issue (24): 5884-5896    DOI: 10.19595/j.cnki.1000-6753.tces.171718
电力电子 |
静止同步补偿器与直驱永磁风机的次同步控制交互研究
任必兴, 杜文娟, 王海风
新能源电力系统国家重点实验室(华北电力大学) 北京 102206
Analysis on Sub-Synchronous Control Interaction between Static Synchronous Compensator and Permanent Magnet Synchronous Generator
Ren Bixing, Du Wenjuan, Wang Haifeng
State Key Laboratory of Alternate Electric Power Systems with Renewable Energy Resources North China Electric Power University Beijing 102206 China
全文: PDF (59022 KB)  
输出: BibTeX | EndNote (RIS)      
摘要 从开环模式谐振角度分析风电场中静止同步补偿器(STATCOM)与多台直驱永磁风机(PMSG)之间的次同步控制交互(SSCI)作用,详细推导并网STATCOM的开环线性化分析模型,并建立含STATCOM与多台PMSG的全系统的闭环线性化互联模型。当STATCOM控制参数调节不恰当时,其与PMSG会发生开环模式谐振,诱发次同步控制交互。基于残差理论,提出一项模式谐振估测指标,能够有效评估STATCOM与PMSG因开环模式谐振引起的SSCI影响。算例分析表明:当发生模式谐振时,STATCOM与PMSG之间的无功控制交互影响要远强于直流电压控制交互,可能引发剧烈的次同步振荡失稳,非线性时域仿真结果证明了理论分析的正确性;PMSG输出功率与模式谐振诱发的SSCI作用成正比,电气设备间距、电网强度与SSCI成反比;STATCOM恒电压控制比恒无功控制对系统稳定的威胁更大。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
任必兴
杜文娟
王海风
关键词 静止同步补偿器多台直驱永磁风机次同步控制交互开环模式谐振估测指标    
Abstract:This paper mainly investigates sub-synchronous control interaction (SSCI) caused by open-loop modal resonance between static synchronous compensator (STATCOM) and multiple permanent magnet synchronous generators (multi-PMSGs). The open-loop linearized analysis model of the STATCOM is derived, and the closed-loop interconnected dynamic model of the multi-PMSGs power system with a STATCOM is worked out. When the parameters of controllers of STATCOM are not properly turned, open-loop modal resonance may occur between STATCOM and PMSG, triggering the sub-synchronous control interaction. A new estimate index based on the residual theory is proposed to effectively evaluate the SSCI between STATCOM and PMSG caused by open-loop modal resonance. Case study shows that the reactive current control interaction between STATCOM and PMSG is much heavier than DC control interaction in the event of open-loop modal resonance, which may cause severe sub-synchronous oscillation instability. Nonlinear simulation verifies the correctness of the theoretical analysis. It is shown that the output power of PMSG is proportional to the SSCI caused by modal resonance, while the electrical equipment space and power grid strength are inversely proportional to the SSCI. In addition, constant voltage control is more threatening to system stability than constant reactive power control for the STATCOM.
Key wordsStatic synchronous compensator (STATCOM)    multi-permanent magnet synchronous generators (PMSGs)    sub-synchronous control interaction (SSCI)    open-loop modal resonance    estimate index   
收稿日期: 2017-12-18      出版日期: 2018-12-29
PACS: TM712  
基金资助:基金项目 国家重点研发计划(2016YFB0900602)和中央高校基本科研业务(2016XS09)资助项目
通讯作者: 杜文娟 女,1979年生,教授,研究方向电力系统稳定性分析与控制。E-mail: ddwenjuan@qq.com   
作者简介: 任必兴 男,1988年生,博士研究生,研究方向为柔性交流输电(FACTS)、大规模新能源接入电力系统的分析与控制。E-mail: renbixing@126.com
引用本文:   
任必兴, 杜文娟, 王海风. 静止同步补偿器与直驱永磁风机的次同步控制交互研究[J]. 电工技术学报, 2018, 33(24): 5884-5896. Ren Bixing, Du Wenjuan, Wang Haifeng. Analysis on Sub-Synchronous Control Interaction between Static Synchronous Compensator and Permanent Magnet Synchronous Generator. Transactions of China Electrotechnical Society, 2018, 33(24): 5884-5896.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.171718          https://dgjsxb.ces-transaction.com/CN/Y2018/V33/I24/5884