Abstract:An improved saturated core type high temperature superconducting(HTS) fault current limiter is developed in this paper. The model of current-limiting device consists of an AC primary superconducting coil and a DC secondary superconducting coil. When normal operating,iron yokes are saturated by a single DC current in high temperature superconducting coil and no current limiting mode occurs. And at the time of fault,the fault current limiting capability decreases depending on the DC current in DC superconducting winding. An idea is to turn the IGBT2 off and puts a resistor in series with the AC superconducting coil for absorbing the incoming energy into the AC coil,and turn the IGBT1 off to disconnect the DC voltage source from the DC high temperature superconducting coil in order to control the fault current in a pre-set region.The operating principle of the new fault current limiter is discussed,and the effect of parameters variety of high temperature superconducting fault current limiter is analyzed on limiting fault current. The simulation and experimental results show that the waveform distortion of normal alternating current decreases and the harmonics is suppressed by the device,and the device is of good limiting and re-closing capability,and demonstrates that the device can reduce both the steady-state and the transient fault current significantly. The device is of great benefit to improve transient stability and enhance the electrical energy quality of power system.
张晚英,胡雪峰,周辉,佘旺,刘东辉,朱英浩. 改进型饱和铁心高温超导限流器的实验研究[J]. 电工技术学报, 2014, 29(11): 169-176.
Zhang Wanying,Hu Xuefeng,Zhou Hui,She Wang,Liu Donghui,Zhu Yinghao. Experimental Research on an Improved Saturated Core High Temperature Superconducting Fault Current Limiter. Transactions of China Electrotechnical Society, 2014, 29(11): 169-176.
[1] Lee B W,Park K B,Sim J,et al. Design and experiments of novel hybrid type superconducting fault current limiters[J]. IEEE Transactions on Applied Superconductivity,2008,18(2): 624-627. [2] Sung Hun Lim,Young Sun Cho,Hyo Sang Choi,et al. Improvement of current limiting capability of HTSC elements in hybrid type SCFCL[J]. IEEE Transactions on Applied Superconductivity,2007,17(2): 1807-1810. [3] 张晚英,周有庆,赵伟明,等. 偏流切换桥路型高温超导故障限流器的实验研究[J]. 中国电机工程学报,2008,28(6): 116-122. [4] 张晚英,周有庆,赵伟明,等. 改进桥路型高温超导故障限流器的实验研究[J]. 电工技术学报,2010,25(1): 70-76. [5] 朱青,朱英浩,周有庆,等. 改进的双桥混合式桥路型高温超导故障限流器[J]. 电工技术学报,2007,22(2): 39-44. [6] Lee B W,Sim J,Park K B,et al. Practical application issues of superconducting fault current limiters for electric power systems[J]. IEEE Transactions on Applied Superconductivity,2008,18(2): 620-623. [7] Inho Song,Changho Choi,Moohyun Cho. Quench protection system for the superconducting coil of the KSTAR Tokamak[J]. IEEE Transactions on Applied Superconductivity,2007,17(1): 1-6. [8] Warut Suampun,Chiang Hsiao Dong. Critical evalua- tion of methods for estimating stability boundary for transient stability analysis in power systems[C]. Power and Energy Society General Meeting,2010. [9] Hyoungku,Chanjoo Lee,Kwanwoo Nam,et al. Development of a 13.2kV/630A(8.3MVA) high tem- perature superconducting fault current limiter[J]. IEEE Transactions on Applied Superconductivity,2008,18(2): 628-631. [10] Alexander Henning,Axel Wehner,Michael Kurrat. Feasibility study of superconducting current limiter application in a cogeneration plant[J]. IEEE Transac- tions on Applied superconductivity,2009,19(3): 1908- 1912. [11] James Maguire,Doug Folts,Jie Yuan,et al. Develo- pment and demonstration of a fault current limiting HTS cable to be installed in the con Edison grid[J]. IEEE Transactions on Applied Super Conductivity,2009,19(3): 1740-1743. [12] Reza Sharifi,Hossein Heydari. Multiobjective optimiza- tion for hts fault-current limiters based on normalized simulated annealing[J]. IEEE Transactions on Applied Super Conductivity,2009,19(2): 3675-3682. [13] Hossien Heydari,Reza Sharifi. Three-dimensional pareto-optimal design of inductive superconducting fault current limiters[J]. IEEE Transactions on Applied Super Conductivity,2010,20(5): 2301-2311. [14] Nand K Singh,Ryan M Tumilty,Graeme M Burt,et al. System-level studies of a MgB2 superconducting fault-current limiter in an active distribution network [J]. IEEE Transactions on Applied Super Conductivity,2010,20(2): 54-60. [15] Tatsuhiko Nii,Yumi Shouno,Yasuyuki Shirai. Basic experiments on transformer type SCFCL of rewound structure using BSCCO wire[J]. IEEE Transac- tions on Applied Super Conductivity,2009,19(3): 1892-1895. [16] Christian Schacherer,James Langston,Michael Steurer,et al. Power hardware-in-the-loop testing of a YBCO- coated conductor fault current limiting module[J]. IEEE Transactions on Applied Super Conductivity,2009,19(3): 1801-1805. [17] Cai Y,Okuda S,Odake T,et al. Study on three-phase superconducting fault current limiter[J]. IEEE Transac- tions on Applied Super Conductivity,2010,20(3): 1127-1130. [18] Tomonori Koyama,Satoru Yanabu. Study and develo- pment of superconducting fault current limiter with high speed reclosing[J]. IEEE Transactions on Applied Super Conductivity,2009,19(3): 1868-1871.