Identification Method of Shielding Failure and Back Striking Over-Voltage of 1 000kV Transmission Line Based on Hilbert-Huang Transform
Luo Richeng1,Li Wen1,Lu Yi2,Huang Biao3,Hu Zongyu4
1. Changsha University of Science & Technology Changsha 410004 China; 2. China Guodian Yongfu Power Generation Corporation Limited Guilin 541805 China; 3. State Grid Yueyang Power Supply Company Yueyang 414000 China; 4. State Grid Yiyang Power Supply Company Yiyang 413000 China
Abstract:A HHT (Hilbert-Huang Transform)-based lightning shielding failure and back striking identification method on 1 000kV UHV transmission lines is proposed by considering antecedent development. Firstly, its equivalent model is established by ATP-EMTP based software. The effects of antecedent development on lightning over-voltage on transmission lines are investigated. Furthermore, the transient processes of over-voltages of shielding failure and back striking after lightning transmission lines are also analyzed. The lightning over-voltage signal on transmission line is decomposed by using empirical mode decomposition. Hilbert transformation is conducted on the first four intrinsic mode function which includes majority of high-frequency signal. The transformed instantaneous amplitude of IMF will be chosen as characteristic quantity. Meanwhile, its variance contribution rate will be calculated. In this case, the identification of lightning shielding failure and back striking on transmission lines is realized. The simulation and evaluation of measured data show that the method can effectively identify lightning shielding failure and back striking. It also avoids influence of ground resistance and lightning current amplitude. Meanwhile, the drawbacks in current lightning parameters measurement method, such as large workload to obtain data, easy misjudgment, are overcome in our work. The method provides theoretical reference for analysis of lightning protection on transmission lines.
罗日成,李稳,陆毅,黄彪,胡宗宇. 基于Hilbert-Huang变换的1 000kV输电线路雷电绕击与反击识别方法[J]. 电工技术学报, 2015, 30(3): 232-239.
Luo Richeng,Li Wen,Lu Yi,Huang Biao,Hu Zongyu. Identification Method of Shielding Failure and Back Striking Over-Voltage of 1 000kV Transmission Line Based on Hilbert-Huang Transform. Transactions of China Electrotechnical Society, 2015, 30(3): 232-239.
[1] 维列夏金, 吴维韩. 俄罗斯超高压和特高压输电线路防雷运行经验分析[J]. 高电压技术, 1998, 24( 2) : 76-79. Weilie Xiajin, Wu Weihan. The analysis of lightning protection for EHV and UHV transmission line in Russia[J]. High Voltage Engineering, 1998, 24(2): 76-79. [2] 刘振亚. 特高压直流输电技术研究成果专辑[M]. 北京: 中国电力出版社, 2006. [3] 邹贵彬, 高厚磊, 朱峰, 等. 输电线路雷击与故障的积分识别方法[J]. 电力系统保护与控制, 2012, 40(9): 43-48. Zou Guibin, Gao Houlei, Zhu Feng, et al. Integral identification method of lightning stroke and fault for transmission line[J]. Power System Protection and Control, 2012, 40(9): 43-48. [4] 李瑞芳, 吴广宁, 曹晓斌, 等. 输电线路雷电绕击率的三维计算方法[J]. 电工技术学报, 2009, 24(10): 134-138. Li Ruifang, Wu Guangning, Cao Xiaobin, et al. Three- dimensional calculation method on shielding failure rate of transmission lines[J]. Transactions of China Electrotechnical Society, 2009, 24(10): 134-138 [5] 曾嵘, 耿屹楠, 李雨, 等. 高压输电线路先导发展绕击分析模型研究[J]. 高电压技术, 2008, 34(10): 2041-2046. Zeng Rong, Geng Yinan, Li Yu, et al. Lightning shielding failure model of transmission line based on leader progress model[J]. High Voltage Engineering, 2008, 34(10): 2041-2046. [6] 肖萍, 汪沨, 黄福勇, 等. 基于连续先导的线路绝缘闪络判据的研究[J]. 电网技术, 2012, 36(11): 271-276. Xiao Ping, Wang Feng, Huang Fuyong, et al. Research on criterion for line insulation flashover based on development of continuous leader[J]. Power System Technology, 2012, 36(11): 271-276. [7] Taniguchi S, Okabe S, Takahashi T, et al. Discharge characteristics of 5m long air gap under foggy condi- tions with lightning shielding of transmission line[J]. IEEE Transactions on Dielectrics and Electrical Insula- tion, 2008, 15(4): 1031-1037. [8] 陈仕龙, 束洪春, 谢静, 等. 特高压直流输电线路故障暂态信号高频特性研究[J]. 电力系统保护与控制, 2012, 40(21): 84-89. Chen Shilong, Shu Hongchun, Xie Jing, et al. High frequency characteristic analysis of fault transient signal at UHVDC transmission lines fault[J]. Power System Protection and Control, 2012, 40(21): 84-89. [9] 齐冲. 高压输电线路雷电绕击和反击的识别[D]. 南宁: 广西大学, 2007. [10] 翟进乾. 配电线路在线故障识别与诊断方法研究[D]. 重庆: 重庆大学, 2012. [11] 吴文辉, 曹祥麟. 电力系统电磁暂态计算与EMTP应用[M]. 北京: 中国水利水电出版社, 2012. [12] Yamada T, Mochiznki A. Experimental evaluation of a LTHV tower model for lightning surge analysis[J]. IEEE Transactions on Power Delivery, 1999, 10(1): 630-635. [13] Yang Pengcheng, Chen Shuiming, He Jinliang, et al. Lightning impulse corona characteristic of 1 000kV UHV transmission lines and its influences on light- ning overvoltage analysis results[J]. IEEE Transac- tions on Power Delivery, 2013, 28(4): 2518-2525. [14] Taniguchi S, Okabe S, Asakawa A, et al. Flashover characteristics of long air gaps with negative switching impulses[J]. IEEE Transactions on Dielectrics and Electrical Insulation, 2008, 15(2): 399-406. [15] 刘毅力, 陶学军, 李佳, 等. 基于HHT的风力发电机组滚动轴承故障特征提取[J]. 电力系统保护与控制, 2012, 40(20): 79-82, 88. Liu Yili, Tao Xuejun, Li Jia, et al. Feature extraction of rolling bearing for wind generator based on HHT[J]. Power System Protection and Control, 2012, 40(20): 79-82, 88. [16] Gu F C, Chang H C, Chen F H, et al. Application of the Hilbert-Huang transform with fractal feature enhancement on partial discharge recognition of power cable joints[J]. Science, Measurement & Technology, 2012, 6(6): 440-448. [17] Huang N E, Shen Z, Long S R. A new view of nonlinear water waves: The Hilbert spectrum[J]. Annual Review of Fluid Mechanics, 1999, 31: 417-457. [18] 公茂法, 夏文华, 李国亮, 等. 变压器和应涌流和励磁涌流识别新判据[J]. 电力系统保护与控制, 2012, 40(18): 139-143. Gong Maofa, Xia Wenhua, Li Guoliang, et al. New judgment to identify sympathetic inrush and inrush current[J]. Power System Protection and Control, 2012, 40(18): 139-143.