Transactions of China Electrotechnical Society  2016, Vol. 31 Issue (4): 178-186    DOI:
Orginal Article Current Issue| Next Issue| Archive| Adv Search |
Fault Phase Selection Scheme for Quadruple-Circuit Transmission Lines with Asymmetrical Parameter Based on Single-Ended Electrical Quantities
Liu Qi1, Tai Nengling1, Fan Chunju1, Yu Zhongan2, Shang Jin1
1. School of Electronic Information and Electrical Engineering Shanghai Jiaotong University Shanghai 200240 China;
2. School of Electrical Engineering and Automation Jiangxi University of Science and Technology Ganzhou 341000 China

Download: PDF (502 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  The asymmetrical quadruple-circuit lines have different self-inductances, which cannot be decoupled by the twelve-sequence-component method. Phase-Line decouple method is adopted to eliminate the mutual inductance, and convert the original phase currents into 12 different independent current components. When a line fault occurs, the boundary conditions help to find out the relationship between the current components. If a fault occurs on different lines, the across components and loop components are in the same or inverse phase. The amplitudes of the components are the same while the phases are shifted a special angle during the same kind of fault on the different phase of same line. Considering the influence of the distributed factors, a fault phase selection method for asymmetrical quadruple-circuit lines is presented, flow chart for fault phase is also provided. The PSCAD/EMTDC simulation results show that this method is suitable for fault phase selection, and the fault location and fault resistance has little influence on this method.
Key wordsAsymmetrical parameter      quadruple line on the same tower      line selection      phase selection      sequence component      single terminal electric quantities     
Published: 03 March 2016
PACS: TM773  
Fund:国家自然科学基金资助项目(51177066、51377104)
Corresponding Authors: 刘 琦 男,1987年生,博士研究生,研究方向为电力系统保护与控制。E-mail: LiuQi8165@163.com   
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Liu Qi
Tai Nengling
Fan Chunju
Yu Zhongan
Shang Jin
Cite this article:   
Liu Qi,Tai Nengling,Fan Chunju等. Fault Phase Selection Scheme for Quadruple-Circuit Transmission Lines with Asymmetrical Parameter Based on Single-Ended Electrical Quantities[J]. Transactions of China Electrotechnical Society, 2016, 31(4): 178-186.
URL:  
https://dgjsxb.ces-transaction.com/EN/     OR     https://dgjsxb.ces-transaction.com/EN/Y2016/V31/I4/178
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech