Transactions of China Electrotechnical Society  2015, Vol. 30 Issue (23): 116-125    DOI:
Current Issue| Next Issue| Archive| Adv Search |
Study on Short Circuit Current and Fault Analysis Method of Double Fed Induction Generator with Low Voltage Ride-through Control Strategy
Yin Jun, Bi Tianshu, Xue Ancheng, Yang Qixun
State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources North China Electric Power University Beijing 102206 China

Download: PDF (3065 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  The enlarged scale of doubly-fed induction generator (DFIG) is connected to the power system and mostly DFIG units generally have a low voltage ride through (LVRT) capability recently.The LVRT property will have notable influences on the short circuit currents in DFIG’s fault.Then the imprecise short-circuit current calculation may affect the results of system fault analysis and thus contribute considerable errors to the evaluation of the protection action characteristic.In this paper,according to the input-output characteristic of the converter,the equivalent model and the transient model of DFIG are provided.The influence mechanism of the LVRT control strategy is analyzed,and the short circuit current calculation model of DFIG is established.Based on the real time digital simulator (RTDS),the experiment platform with physical controller is founded,by which the proposed short-circuit current calculating model is validated.The fault analysis method for the grid with penetration of DFIG is analyzed.Results of this research are available for the study of the influence of DFIG on the protection characteristics.
Key wordsDoubly-fed induction generator      low voltage ride through      short circuit current      relay     
Received: 24 April 2015      Published: 18 December 2015
PACS: TM711  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Yin Jun
Bi Tianshu
Xue Ancheng
Yang Qixun
Cite this article:   
Yin Jun,Bi Tianshu,Xue Ancheng等. Study on Short Circuit Current and Fault Analysis Method of Double Fed Induction Generator with Low Voltage Ride-through Control Strategy[J]. Transactions of China Electrotechnical Society, 2015, 30(23): 116-125.
URL:  
https://dgjsxb.ces-transaction.com/EN/     OR     https://dgjsxb.ces-transaction.com/EN/Y2015/V30/I23/116
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech