电工技术学报  2021, Vol. 36 Issue (17): 3605-3613    DOI: 10.19595/j.cnki.1000-6753.tces.201469
电力装备智能感知与智能终端 |
电磁式电压互感器“低频过电压激励-响应”逆问题求解
杨鸣1, 熊钊1, 司马文霞1, 李永福2, 何东升3, 邹滨阳1
1.输配电装备及系统安全与新技术国家重点实验室(重庆大学) 重庆 400030;
2.国网重庆市电力公司重庆电力科学研究院 重庆 401123;
3.国家智能电网输配电设备质量监督检验中心 东莞 523325
Solution of the Inverse Problem of “Low-Frequency Overvoltage Excitation to Response” for Electromagnetic Potential Transformers
Yang Ming1, Xiong Zhao1, Sima Wenxia1, Li Yongfu2, He Dongsheng3, Zou Binyang1
1. State Key Laboratory of Power Transmission Equipment & System Security and New Technology Chongqing University Chongqing 400030 China;
2. State Grid Chongqing Electric Power Company Chongqing Electric Power Research Institute Chongqing 401123 China;
3. China National Quality Supervision and Testing Center for Smart Grid Transmission and Distribution Equipment Dongguan 523325 China
全文: PDF (1449 KB)   HTML
输出: BibTeX | EndNote (RIS)      
摘要 电磁式电压互感器(PT)作为电力系统中已大规模应用的电压感知设备,在低频电磁暂态电压激励下可能出现铁心饱和,引起二次响应电压波形畸变、测量误差激增。通过求解PT的“低频过电压激励-响应”逆问题,由PT二次响应电压计算得到其一次激励电压。该文基于电磁对偶原理建立计及铁心深度饱和特性的PT正向电路模型及其参数提取方法,进而构建其逆向数学模型,提出PT“低频过电压激励-响应”逆问题的求解方法。针对10kV真型PT的低频暂态仿真与试验数据进行“低频过电压激励-响应”逆问题求解方法的验证,结果表明:提出的逆向求解方法可将PT的低频电磁暂态测量误差从65.6%降低至10%,解决了其在低频暂态电压激励下的测量失真难题。
服务
把本文推荐给朋友
加入我的书架
加入引用管理器
E-mail Alert
RSS
作者相关文章
杨鸣
熊钊
司马文霞
李永福
何东升
邹滨阳
关键词 电磁式电压互感器低频暂态电压深度饱和特性逆问题求解    
Abstract:Electromagnetic potential transformer(PT)is a piece of critical voltage measurement equipment widely used in power systems. However, low-frequency electromagnetic transient voltages may excite the core of PT to be saturated, resulting in a significant increase in measurement error. By solving the inverse problem of “low-frequency overvoltage excitation to response” of PT, its primary excitation voltage can be calculated based on the secondary response voltage. Based on the principle of electromagnetic duality, a forward circuit model considering the deep saturation of the iron core and its parameters extraction method are proposed in this paper, then an inverse mathematical model is constructed, which solves the inverse problem of “low-frequency overvoltage excitation to response” of PT. The proposed method is validated by simulations and experiments on a 10kV PT. Results show that the proposed method can significantly decrease the error of the PT from 65.6% to 10%, when it suffers from deep saturation caused by low-frequency transients. The proposed method solves the problem of distortion of the secondary voltage of the PT under the excitation of low-frequency transients.
Key wordsElectromagnetic potential transformer    low-frequency transient voltage    deep saturation characteristics    inverse problem solving   
收稿日期: 2020-11-01     
PACS: TM451+.1  
  TM835.1  
基金资助:国家自然科学基金重点项目(51837002)和国家自然科学基金面上项目(51977018)资助
通讯作者: 司马文霞 女,1965年生,博士,教授,博士生导师,教育部“长江学者”特聘教授,研究方向为电力系统的防雷与过电压防护、特殊环境中外绝缘放电特性及机理。E-mail:cqsmwx@cqu.edu.cn   
作者简介: 杨 鸣 男,1987年生,博士,副教授,博士生导师,研究方向为变压器类设备建模,高电压输变电技术及电力系统过电压。E-mail:cqucee@cqu.edu.cn
引用本文:   
杨鸣, 熊钊, 司马文霞, 李永福, 何东升, 邹滨阳. 电磁式电压互感器“低频过电压激励-响应”逆问题求解[J]. 电工技术学报, 2021, 36(17): 3605-3613. Yang Ming, Xiong Zhao, Sima Wenxia, Li Yongfu, He Dongsheng, Zou Binyang. Solution of the Inverse Problem of “Low-Frequency Overvoltage Excitation to Response” for Electromagnetic Potential Transformers. Transactions of China Electrotechnical Society, 2021, 36(17): 3605-3613.
链接本文:  
https://dgjsxb.ces-transaction.com/CN/10.19595/j.cnki.1000-6753.tces.201469          https://dgjsxb.ces-transaction.com/CN/Y2021/V36/I17/3605