Abstract:The gird-connected photovoltaic (PV) inverters usually operate in low utilization for diurnal variations and weather changes. A new strategy for three-phase grid-connected PV generation systems is proposed, which has the shunt active power filter function. The strategy is based on load-level judgment and load-type identification, whose synthetic methods of instruction current is given. The new strategy not only makes full use of PV power, but also compensates harmonics and reactive currents of the loads very well, especially when the loads are in low level. The system response speed would be improved quickly without harmonics current detection. The new configuration adopts the DC/DC/AC high frequency link main circuits, which overcomes the shortcoming of the power frequency transformer's serious supplies in the traditional PV gird-connected systems. With the modeling and simulation of the proposed control strategy by Matlab/Simulink, the experimental results show that the control strategy is validated.
杜春水, 张承慧, 刘鑫正, 陈阿莲. 带有源电力滤波功能的三相光伏并网发电系统控制策略[J]. 电工技术学报, 2010, 25(9): 163-169.
Du Chunshui, Zhang Chenghui, Liu Xinzheng, Chen Alian. Control Strategy on the Three-Phase Grid-Connected Photovoltaic Generation System With Shunt Active Power Filter. Transactions of China Electrotechnical Society, 2010, 25(9): 163-169.
[1] Zeng Qingrong, Chang Liuchen. Study of advanced current control strategies for three phase grid-connected PWM inverters for distributed generation[C]. Proc. IEEE Control Applications, Canada, 2005: 1311-1316. [2] 杨海柱, 金新民. 最大功率跟踪的光伏并网逆变器研究[J]. 北方交通大学学报, 2004, 28(2): 65-68. [3] 张承慧, 叶颖, 陈阿莲, 等. 基于输出电流控制的光伏并网逆变电源[J]. 电工技术学报, 2007, 22(8): 41-45. [4] 姜齐荣, 赵东元, 陈建业. 有源电力滤波器[M]. 北京:科学出版社, 2005. [5] Wu Tsai Fu, Nien Huang Shou, et al. PV power injection and active power filtering with amplitude- claming and amplitude-scaling algorithms[J]. IEEE Trans. on Industry Application, 2007, 43(3): 731-741. [6] 吴浩伟, 段善旭, 徐正喜. 一种新颖的电压控制型逆变器并网控制方案[J]. 中国电机工程学报, 2008, 28(33): 19-24. [7] 张国荣, 张铁良, 丁明, 等. 光伏并网发电与有源电力滤波器的统一控制[J]. 电力系统自动化, 2007, 31(8): 61-65. [8] 吴理博, 赵争鸣, 刘建政, 等. 具有无功补偿功能的单极式三相光伏并网系统[J]. 电工技术学报, 2006, 21(1): 28-32. [9] Cho J G, Baek J W, Jeong C Y, et al. Novel zero-voltage and zero-current-switch-ing (ZVZCS) full bridge PWM converter using a simple Auxiliary circuit[C]. IEEE Applied Power Electronics Conference and Exposition, 1998: 834-839. [10] Cheng K W Eric. Switched mode power conversion for alternative energy[J]. Control Theory & Application, 2008, 225(1): 125-132. [11] 王兆安, 杨君, 刘进军, 等. 谐波抑制和无功补偿[M]. 北京: 机械工业出版社, 2005. [12] Bum Sik K, Won Hyun O, Eun Chul S, et al. Current control method using a double band hysteresis[C]. IECON 2004, 30th Annual Conference of IEEE, Busan, Korea, 2004: 286-290. [13] Akagi H, Kanazawa Y, Nabae A. Generalized theory of instantaneous reactive power and its application[C]. IEEE & JIEE. Proceedings IPEC, Tokyo, 1983: 1375- 1386. [14] 田大强, 蒋平, 唐国庆. 有源滤波器中数字低通滤波器设计及其实现[J].电工电能新技术, 2002, 22(3): 77-80. [15] Salas V, Olías E, Lázaro A, et al. New algorithm using only one variable measurement applied to a maximum power point tracker[J]. Solar Energy Materials & Solar Cells, 2005, 87(1-4): 675-684.