Influence of Unbalance Arcing Energy Between Two Breaks of a Double-Break MCCB |
Liu Hongwu1, 2, Xie Xinyi1, He Yanfeng1, Chen Degui2 |
1. Changshu Switchgear Mfg. Co., Ltd. Changshu 215500 China 2. Xi’an Jiaotong University Xi’an 710049 China |
|
|
Abstract Through experimental observation, this paper put forward that the arcing energy between the two gaps of a double-break MCCB may be unbalanced in breaking operation, and this may exert negative influence on the breaking performance of MCCB. Based on further study and experiment, back-commutation is confirmed to be the main cause for the unbalance issue; consequently by constraining of back-commutation, the balance can be approached through the means of reasonable designing.
|
Received: 14 December 2008
Published: 04 March 2014
|
|
|
|
|
[1] Wolfgang Hauer, Peter Zeller, Xin Zhou.Benchmark tests of single-break and double-break design principles[C]. Proceedings of the 53th IEEE Holm Conference on Electrical Contacts, 2007: 48-55. [2] 张波, 陈德桂. 旋转双断点塑壳断路器机构的动态仿真与优化[J]. 低压电器, 2007(13): 5-7. [3] 楼梅燕, 郑跃胜. 桥式双断点塑料外壳式断路器磁场分析[J]. 低压电器, 2009(1): 14-16. [4] 刘洪武, 陈德桂, 李兴文, 等. 采用自聚焦透镜的开关电弧运动形态光纤测试系统[J]. 中国电机工程学报, 2003, 23(9): 126-131. [5] Yoshiyuki Ikuma, Yukio Kito. Influence of deion plate configuration and arc column behaviour on the arc voltage waveforms in low-voltage molded-case circuit breakers[J]. Transactions IEE Japan, 1988, 108-B(3): 863-866. [6] Lindmayer M. Simulation of stationing current- voltage characteristics and of back-commutation in rectangular arc channels[C]. 17th International Conference on Electrical Contacts, Nagova , 1994: 65-77. [7] Fievet C , Chevrier P, Andre V, et al. Experimental study of back commutation in low voltage circuit breaker[C]. IEEE International Conference on Plasma Science, Boston, 1996: 122-123. [8] Gauster E, Rieder W. Back-commutation in low voltage interrupters: influence of recovery time, geometry and materials of contacts and walls[C]. 43th IEEE Holm Conference on Electrical Contacts, 1997: 91-96. [9] Lindmayer M, Huang Z. Switching arcs squeezed in rectangular insulating slots-scaling laws and comparison with measurements[J]. European Transactions on Electrical Power, 1991, 1(2): 107-111. [10] 陈旭, 陈德桂. 新型灭弧系统对背后击穿现象的抑制作用[J]. 低压电器, 2000(3): 9-12. [11] 陈德桂. 低压断路器电弧背后击穿现象的研究[J]. 低压电器, 1999(6): 7-10. |
|
|
|