Transactions of China Electrotechnical Society  2016, Vol. 31 Issue (1): 14-23    DOI:
Original Articles Current Issue| Next Issue| Archive| Adv Search |
The Fault Calculation Method of Power Systems Including Doubly-fed Induction Generators
Xiao Fan1,Zhang Zhe1,Yin Xianggen1,Yang Hang1,Yang Zengli2
1.State Key Laboratory of Advanced Electromagnetic Engineering and Technology Huazhong University of Science and Technology Wuhan 430074 China
2.State Grid Hubei Electric Power Company Wuhan 430077 China

Download: PDF (2880 KB)   HTML (1 KB) 
Export: BibTeX | EndNote (RIS)      
Abstract  The complex fault current characteristics of doubly-fed induction generators (DFIGs) cause that the conventional fault analysis method based on AC synchronous generators is not applicable for the power systems containing DFIGs.According to the low voltage ride through (LVRT) control strategy of the DFIGs,the short-circuit calculation models of the DFIGs are established considering their excitation regulation characteristics for the three-phase fault or the unbalanced fault.Based on this,the sequence networks of the power systems containing DFIGs are proposed using the symmetrical component method.According to the nodal voltage equations,the fault boundary conditions equation,and the short-circuit calculation models of DFIGs,the branch currents and the node voltages are calculated based on an iterative algorithm.The simulation results show that the proposed method has a high accuracy of short-circuit current calculation and can meet the requirements of engineering applications.
Key wordsDFIGs      short-circuit calculation      low voltage ride through      equivalent model      iterative algorithm     
Received: 20 January 2015      Published: 21 January 2016
PACS: TM74  
Service
E-mail this article
Add to my bookshelf
Add to citation manager
E-mail Alert
RSS
Articles by authors
Xiao Fan
Zhang Zhe
Yin Xianggen
Yang Hang
Yang Zengli
Cite this article:   
Xiao Fan,Zhang Zhe,Yin Xianggen等. The Fault Calculation Method of Power Systems Including Doubly-fed Induction Generators[J]. Transactions of China Electrotechnical Society, 2016, 31(1): 14-23.
URL:  
https://dgjsxb.ces-transaction.com/EN/     OR     https://dgjsxb.ces-transaction.com/EN/Y2016/V31/I1/14
Copyright © Transactions of China Electrotechnical Society
Supported by: Beijing Magtech