Abstract:The new method of operating an inverter to imitate a synchronous generator for circulating current restraint is motivated and developed. Based on the comparison with the traditional droop control method, detail analysis is done on the principles of decoupling between the equivalent line impedance and output reactive power and the advantage of the new method to improving the accuracy of the load power distribution is described. In order to reduce voltage and frequency difference between the paralleled inverters when no-load operating, minor amendment is used to the droop control coefficient to meet the demand of load power distribution between different rated power inverters and circulation suppression and adding differential link to improve the control delays caused by power calculation. Simulation and experiment are done in a small-scale experimental micro-grid system which contains two inverters in parallel. The results are given to verify that the circulation inhibitory is effective in a variety of conditions.
吕志鹏, 罗安, 蒋雯倩, 徐欣慰. 多逆变器环境微网环流控制新方法[J]. 电工技术学报, 2012, 27(1): 40-47.
Lü Zhipeng, Luo An, Jiang Wenqian, Xu Xinwei. New Circulation Control Method for Micro-Grid with Multi-Inverter Micro-Sources. Transactions of China Electrotechnical Society, 2012, 27(1): 40-47.
[1] 余贻鑫, 栾文鹏. 智能电网述评[J]]. 中国电机工程学报, 2009, 29(34): 1-6. Yu Yixin, Luan Wenpeng. Smart grid and its implementations [J]. Proceedings of the CSEE, 2009, 29(34): 1-6. [2] 鲁宗相, 王彩霞, 闵勇, 等. 微电网研究综述[J]. 电力系统自动化, 2007, 31(19): 101-102. Lu Zongxiang, Wang Caixia, Min Yong, et al. Overview on micro-grid research[J]. Automation of Electric Power Systems, 2007, 31(19): 101-102. [3] 陈达威, 朱桂萍. 低压微电网中的功率传输特性[J]. 电工技术学报, 2010, 25(7): 117-122. Chen Dawei, Zhu Guiping. Power transmission characteristics of low voltage microgrids[J]. Transactions of China Electrotechnical Society, 2010, 25(7): 117-122. [4] 吕志鹏, 罗安, 荣飞, 等. 电网电压不平衡条件下微网PQ控制策略研究[J]. 电力电子技术, 2010, 44(6): 71-74. Lü Zhipeng, Luo An, Rong Fei, et al. Micro-grid PQ control strategy analysis under utility voltage imbalance[J]. Power Electronics, 2010, 44(6): 71-74. [5] Murakamia A, Yokoyama A, Tada Y. Basic study on battery capacity evaluation for load frequency control(LFC) in power system with a large penetration of wind power generation[J]. IEEJ Transactions on Power and Energy, 2006, 126(2): 236-241. [6] Qing-Chang Zhong, Weiss G. Static synchronous generators for distributed generation and renewable energy[C]. IEEE/PES Power Systems Conference and Exposition, 2009: 1-6. [7] Sao C K, Lehn P W. Autonomous load sharing of voltage source converters[J]. IEEE Transactions Power Delivery, 2005, 20(2): 1009-1016. [8] Brabandere K D, Bolsens B, Keybus J V, et al. A voltage and frequency droop control method for parallel inverters[J]. IEEE Transactions on Power Electronics, 2007, 22(4): 1107-1115.