A Two-Stage Decentralized Robust Optimization Method for Computing Power-Electricity-Heat Coordination in Edge Data Center Cluster
Sun Yi1,2, Zhang Kai1,2, Gegen Aoqi1,2, Wu Peng3, Zhu Jin4
1. School of Electrical and Electronic Engineering North China Electric Power University Beijing 102206 China; 2. Engineering Research Center of Electricity Conversion and Intelligent Electricity Use Ministry of Education North China Electric Power University Beijing 102206 China; 3. State Grid Energy Research Institute Co. Ltd Beijing 102209 China; 4. State Grid Jiangsu Electric Power Co. Ltd Nanjing 210024 China
Abstract:The rapid development of the digital economy and the advancement of new infrastructure have driven explosive growth in the deployment of edge data center (EDC). Consequently, their escalating energy consumption has become a critical bottleneck for the sustainable development of edge computing. Characterized by small scale, high power density, and urban clustering into edge data center cluster (EDCC), EDCs exhibit tightly coupled and dynamic interactions across the computing power-electricity-heat domains. However, existing operational strategies typically lack precision in thermal environment control, flexibility in managing dual source-load uncertainties, and depth in multi-energy flow coordination. To address these challenges, this paper first establishes a refined computing power-electricity-heat model for the EDCC. Leveraging Willems’ Fundamental Lemma and model predictive control (MPC), we construct an implicit rack-level thermal control model. This model integrates data load processing with the operation of external cooling infrastructure to achieve tight coordination of multi-energy flows. Second, to address the dual uncertainties from distributed photovoltaic (DPV) intermittency and fluctuating data load arrivals, we develop a two-stage distributionally robust optimization (DRO) model. The ambiguity set for this model is constructed using joint Kullback-Leibler (KL) divergence. The day-ahead stage (first-stage) determines the operation of external cooling infrastructure and server on/off states. The intra-day stage (second-stage) optimizes cross-EDC energy sharing, heterogeneous server load allocation, temporal data load shifting, and the scheduling of computer room air handlers (CRAH) and uninterruptible power supply (UPS) units. Furthermore, to balance computational efficiency and privacy preservation in large-scale optimization, we design an Inexact column and constraint generation (IC&CG) algorithm, nested with an adaptive alternating direction method of multipliers (ADMM). The IC&CG handles the master problem, while the adaptive ADMM solves subproblems in parallel Case studies are conducted on the Matlab simulation platform and industry-recognized data center thermal environment simulation software. Performance is systematically evaluated across four dimensions: (1) Operational strategy effectiveness, validating the EDCC energy sharing mechanism and the coordinated cooling control strategy; (2) refined thermal control performance, benchmarking against traditional static PUE-based control and lumped-parameter MPC methods; (3) joint uncertainty handling, comparing the proposed method with deterministic optimization, stochastic optimization, robust optimization, and DRO based on independent uncertainty modeling; (4) algorithm performance, comparing the proposed IC&CG-adaptive ADMM against centralized C&CG and standard C&CG-ADMM. Simulation results confirm the core advantages of our method: the rack-level temperature control achieves a root mean square error (RMSE) of only 0.39℃. Compared to deterministic optimization, our approach reduces the median EDCC operating cost by 4.51% and the 99% quantile tail risk by 13.62%, achieves a cluster-wide power usage effectiveness (PUE) of 1.22, and shortens the solution time by 69.68%. Based on the above analysis, the main conclusions are as follows: (1) The refined EDCC model and implicit rack-level thermal control effectively unlock the operational regulation potential, optimizing overall energy efficiency. (2) The two-stage DRO model based on joint KL divergence effectively mitigates uncertainties from DPV and data loads; adjusting the KL divergence threshold allows for a dynamic trade-off between robustness and economy. (3) Compared to traditional centralized architectures, the distributed IC&CG-adaptive ADMM algorithm efficiently solves large-scale, multi-energy coupled problems under decentralized information structures, ensuring solution accuracy while significantly reducing computation time.
孙毅, 张凯, 格根敖其, 吴鹏, 朱进. 边缘数据中心集群算力-电力-热力协同的两阶段分布鲁棒优化[J]. 电工技术学报, 2026, 41(21): 7257-7279.
Sun Yi, Zhang Kai, Gegen Aoqi, Wu Peng, Zhu Jin. A Two-Stage Decentralized Robust Optimization Method for Computing Power-Electricity-Heat Coordination in Edge Data Center Cluster. Transactions of China Electrotechnical Society, 2026, 41(21): 7257-7279.
[1] 华为技术有限公司. 面向5G的边缘数据中心基础设施[R]. 深圳: 华为技术有限公司, 2019. [2] Zhang Yingbo, Shan Kui, Li Xiuming, et al.Research and technologies for next-generation high-temperature data centers-state-of-the-arts and future perspectives[J]. Renewable and Sustainable Energy Reviews, 2023, 171: 112991. [3] Zhu Yiqun, Zhang Quan, Zeng Liping, et al.An advanced control strategy of hybrid cooling system with cold water storage system in data center[J]. Energy, 2024, 291: 130304. [4] Zhu Yiqun, Zhang Quan, Huang Gongsheng, et al.The influence of uncertainty parameters on the double-layer model predictive control strategy for the collaborative operation of chiller and cold storage tank in data center[J]. Energy, 2024, 313: 133866. [5] 可思为, 董萍, 马铭宇, 等. 考虑风光荷时空互补的多能源绿色数据中心多目标配置方法[J]. 电力系统保护与控制, 2024, 52(22): 22-33. Ke Siwei, Dong Ping, Ma Mingyu, et al.A multi-objective allocation method for multi-energy green data centers considering wind, solar and load spatial-temporal complementarity[J]. Power System Protec-tion and Control, 2024, 52(22): 22-33. [6] 马浩天, 胡俊杰, 童宇轩. 考虑灵活性的数据中心微网两阶段鲁棒规划方法[J]. 中国电机工程学报, 2023, 43(19): 7396-7408. Ma Haotian, Hu Junjie, Tong Yuxuan.A two-stage robust planning approach for data center microgrids considering flexibility[J]. Proceedings of the CSEE, 2023, 43(19): 7396-7408. [7] Zhao Jing, Chen Ziyi, Li Haonan, et al.A model predictive control for a multi-chiller system in data center considering whole system energy conservation[J]. Energy and Buildings, 2024, 324: 114919. [8] 朱介北, 杨顺坡, 俞露杰, 等. 数据中心制冷系统即时消纳可再生能源的建模和变温控制[J]. 电力系统自动化, 2022, 46(20): 13-22. Zhu Jiebei, Yang Shunpo, Yu Lujie, et al.Modeling and variable temperature control for instant consumption of renewable energy in data center cooling systems[J]. Automation of Electric Power Systems, 2022, 46(20): 13-22. [9] Lu Ruyuan, Li Xin, Chen Ronghao, et al.An alternative reinforcement learning (ARL) control strategy for data center air-cooled HVAC systems[J]. Energy, 2024, 308: 132977. [10] 马浩然, 袁至, 王维庆, 等. 考虑数据中心和储能接入的主动配电网经济调度研究[J]. 发电技术, 2025, 46(4): 748-757. Ma Haoran, Yuan Zhi, Wang Weiqing, et al.Research on economic scheduling of active distribution networks with inclusion of data center and energy storage[J]. Power Generation Technology, 2025, 46(4): 748-757. [11] 文亚凤, 程祖铭, 刘欣雅, 等. 考虑算力-电热耦合的边缘数据中心能量优化管理[J]. 中国电机工程学报, 2026, 46(1): 186-197. Wen Yafeng, Cheng Zuming, Liu Xinya, et al.Energy optimization management of edge data centers considering computing power-electrothermal coupling[J]. Proceedings of the CSEE, 2026, 46(1): 186-197. [12] Li Xiaoping, Chen Fuchao, Ruiz R, et al.MapReduce task scheduling in heterogeneous geo-distributed data centers[J]. IEEE Transactions on Services Computing, 2022, 15(6): 3317-3329. [13] 王继东, 许秋铭, 黄婷, 等. 含共享储能的数据中心微网群分布式优化调度[J]. 电网技术, 2024, 48(8): 3238-3247. Wang Jidong, Xu Qiuming, Huang Ting, et al.Distributed optimal scheduling of data center microgrids cluster with shared energy storage[J]. Power System Technology, 2024, 48(8): 3238-3247. [14] De Melo da Silva M, Gamatié A, Sassatelli G, et al. Optimization of data and energy migrations in mini data centers for carbon-neutral computing[J]. IEEE Transactions on Sustainable Computing, 2023, 8(1): 68-81. [15] 张玉莹, 曾博, 周吟雨, 等. 碳减排驱动下的数据中心与配电网交互式集成规划研究[J]. 电工技术学报, 2023, 38(23): 6433-6450. Zhang Yuying, Zeng Bo, Zhou Yinyu, et al.Research on interactive integration planning of data centers and distribution network driven by carbon emission reduction[J]. Transactions of China Electrotechnical Society, 2023, 38(23): 6433-6450. [16] 中国电力发展促进会电力与算力协同发展专业委员会, 紫金山实验室, 江苏省未来网络创新研究院, 等. 电力与算力协同发展蓝皮书(2025)[R]. 北京: 中国电力发展促进会电力与算力协同发展专业委员会, 2025. [17] 张献, 丁可浩, 赵黎媛, 等. 计及电动汽车混合充电系统接入的综合能源系统鲁棒优化调度[J]. 电工技术学报, 2025, 40(14): 4446-4459. Zhang Xian, Ding Kehao, Zhao Liyuan, et al.Robust optimal scheduling of integrated energy system considering electric vehicle hybrid charging system[J]. Transactions of China Electrotechnical Society, 2025, 40(14): 4446-4459. [18] 李虹, 韩雨萌. 计及新能源不确定性的配电网-多微电网协同优化调度[J]. 电工技术学报, 2025, 40(17): 5571-5588. Li Hong, Han Yumeng.Coordinated optimization scheduling of distribution networks and multiple microgrids considering the uncertainty of new energy[J]. Transactions of China Electrotechnical Society, 2025, 40(17): 5571-5588. [19] Wang Zhiying, Wang Yang, Ji Haoran, et al.Distributionally robust planning for data center park considering operational economy and reliability[J]. Energy, 2024, 290: 130185. [20] Li Weiwei, Qian Tong, Zhang Yin, et al.Distributionally robust chance-constrained planning for regional integrated electricity-heat systems with data centers considering wind power uncertainty[J]. Applied Energy, 2023, 336: 120787. [21] Ding Zhaohao, Chen Shijie, Sun Yimeng, et al.Data center job scheduling and energy management under uncertain environments[J]. IEEE Transactions on Industry Applications, 2025, 61(4): 5489-5500. [22] 王波, 王蔚, 马恒瑞, 等. 基于Wasserstein两阶段分布鲁棒的多主体多能微网合作博弈优化调度[J]. 电工技术学报, 2025, 40(17): 5553-5570. Wang Bo, Wang Wei, Ma Hengrui, et al.Multi-agent multi-energy microgrid cooperative game scheduling based on Wasserstein two stage robust optimization[J]. Transactions of China Electrotechnical Society, 2025, 40(17): 5553-5570. [23] 王海伦, 丁一凡, 李杨, 等. 计及混合式抽水蓄能改造的清洁微网分布鲁棒容量优化配置[J]. 电工技术学报, 2025, 40(7): 2112-2126. Wang Hailun, Ding Yifan, Li Yang, et al.Distributionally robust capacity optimization for clean energy microgrid considering pumped-storage retrofitting[J]. Transactions of China Electrotechnical Society, 2025, 40(7): 2112-2126. [24] Ismail L, Materwala H.Computing server power modeling in a data center: survey, taxonomy, and performance evaluation[J]. ACM Computing Surveys, 2021, 53(3): 1-34. [25] 深圳市腾讯计算机系统有限公司, 英特尔(中国)有限公司, 中国电信集团有限公司. 数据中心算力-电力灵活性协同研究[R]. 深圳: 深圳市腾讯计算机系统有限公司, 2023. [26] Zhao Xinkui, Yin Jianwei, Chen Zuoning, et al.vSpec: workload-adaptive operating system specialization for virtual machines in cloud computing[J]. Science China Information Sciences, 2016, 59(9): 92105. [27] 华为技术有限公司. 计算产品能耗计算器[EB/OL].[2025-08-06]. https://info.support.huawei.com/computing/ftpa/. [28] 刘素梅, 徐文成, 孙曦冉, 等. 交直流微电网互联变换器功率协调自抗扰控制策略[J]. 发电技术, 2026, 47(1): 195-203. Liu Sumei, Xu Wencheng, Sun Xiran, et al.Active disturbance rejection control strategy for power coordination of interlinking converters in AC/DC microgrids[J]. Power Generation Technology, 2026, 47(1): 195-203. [29] 张虹, 郑广宇, 娄娟, 等. 计及热电负荷不匹配的数据中心余热补偿系统调控策略[J]. 电力系统自动化, 2025, 49(13): 156-165. Zhang Hong, Zheng Guangyu, Lou Juan, et al.Regulation strategy of waste heat compensation system for data center considering thermo-electric load mismatch[J]. Automation of Electric Power Systems, 2025, 49(13): 156-165. [30] 连之伟. 热质交换原理与设备[M]. 3版. 北京: 中国建筑工业出版社, 2011. [31] 曾博, 孟自帅, 董嘉路, 等. 考虑电-水耦合灵活性的数据中心与城市配电-水网协同规划研究[J]. 电工技术学报, 2025, 40(23): 7554-7569. Zeng Bo, Meng Zishuai, Dong Jialu, et al.Research on synergistic planning of data center and urban electricity-water distribution networks considering electricity-water interdependent flexibility[J]. Transactions of China Electrotechnical Society, 2025, 40(23): 7554-7569. [32] Isazadeh A, Ziviani D, Claridge D E.Thermal management in legacy air-cooled data centers: an overview and perspectives[J]. Renewable and Sus-tainable Energy Reviews, 2023, 187: 113707. [33] Li Xiuming, Zhang Ce, Dong Jiaxiang, et al.Feasibility investigation on a novel rack-level cooling system for energy-saving retrofit of medium-and-small data centers[J]. Applied Thermal Engineering, 2023, 229: 120644. [34] Li Yiran, Yang Chao, Xia Yuanqing.A robust data-driven model predictive thermal control for rack-based data center[J]. Journal of Building Engineering, 2024, 98: 110877. [35] Liu Weiwei, Tong Xiaoxi, Wang Jiaqiang, et al.Real-time temperature predictions via state-space model and parameters identification within rack-based cooling data centers[J]. Journal of Building Engineering, 2022, 58: 105013. [36] Wang Chenchao, Meng Deyuan.Data-based optimization control for learning systems[J]. IEEE Transactions on Circuits and Systems II: Express Briefs, 2023, 70(7): 2560-2564. [37] Wei Danxiang, Wang Jianzhou, Li Zhiwu, et al.Wind power curve modeling with hybrid copula and grey wolf optimization[J]. IEEE Transactions on Sustainable Energy, 2022, 13(1): 265-276. [38] Wang Zhongliang, Zhu Hongyu, Zhang Dongdong, et al.Modelling of wind and photovoltaic power output considering dynamic spatio-temporal correlation[J]. Applied Energy, 2023, 352: 121948. [39] 梁俊文, 林舜江, 刘明波, 等. 主动配电网分布式鲁棒优化调度方法[J]. 电网技术, 2019, 43(4): 1336-1344. Liang Junwen, Lin Shunjiang, Liu Mingbo, et al.Distributed robust optimal dispatch in active distribution networks[J]. Power System Technology, 2019, 43(4): 1336-1344.