Analysis of Influence of Two Static Conductors on the Interruption Performance of MCCB |
Ji Liang1, Chen Degui1, Liu Yingyi2, Li Xingwen1 |
1. Xi'an Jiaotong University Xi'an 710049 China 2. Beihang University Beijing 100084 China |
|
|
Abstract Well-designed structure of the static conductor is helpful for improving the interruption performance of MCCB. Electro-dynamic force and magnetic field of the electric arc are calculated and compared between circuit breakers using two different static conductors. Based on the calculation results, influencing factors affected by the static conductor structure, including the contact separation time, the repulsive electro-dynamic force acting on the contact, the magnetic field distribution in the electric arc and the magnetic field magnitude during arc ignition, are analyzed. According to the analysis result, improvement of the static conductor structure of an actual MCCB is carried out and found effective of improving its interruption performance by network trial.
|
Received: 03 March 2009
Published: 04 March 2014
|
|
|
|
|
[1] 陈德桂, 戴瑞成, 刘洪武. 弧柱压降对塑壳断路器限流性能的作用[J]. 低压电器, 2005(11): 6-9. [2] 陈德桂. 气吹灭弧与压力脱扣技术促进了低压断路器分断性能提高[J]. 低压电器, 2003(3): 3-6. [3] 刘洪武, 陈德桂, 李志鹏. 不同因素对气吹式塑壳断路器开断电弧运动影响的实验研究[J]. 中国电机工程学报, 2004, 24(11): 154-159. [4] 李兴文, 陈德桂, 汪倩, 等. 低压电器中气动斥力的实验研究[J]. 中国电机工程学报, 2006, 26(15): 83-88. [5] Li Xingwen, Chen Degui, Wang Qian, et al. Simulation of the effects of several factors on arc plasma behavior in low voltage circuit breaker[J]. Plasma Science & Technology, 2005, 7(5): 3069-3072. [6] 李兴文, 陈德桂, 汪倩, 等. 低压塑壳断路器三相短路开断特性的仿真分析[J]. 电工技术学报, 2005, 20(10): 76-82. [7] Shokichi Tto, Yoshiaki Takato. Numerical analysis of electromagnetic forces in low voltage AC circuit breakers using 3-D finite element method taking into account eddy currents[J]. IEEE Transactions on Magnetics, 1998, 34(5): 2597-2600. [8] 李兴文, 陈德桂, 李志鹏, 等. 考虑触头间电流收缩影响的低压塑壳断路器中电动斥力分析[J]. 电工技术学报, 2004, 19(10): 1-5. [9] Stammberger H. Force calculation for the movable contact of circuit breakers[C]. 19th International Conference on Electric Contact Phenomena, Nuremberg, Germany, 1998: 14-17. [10] Yoshihiro Kawase, Hiroyuki Mori, Shikochi Ito. 3-D element analysis of electro-dynamic repulsion force in stationary electric contacts taking into account asymmetric shape[J]. IEEE Transactions on Magnetics, 1997, 33(2): 1994-1999. |
|
|
|