|
|
Experimental Investigating on On-Line Monitoring of Winding Deformation of Power Transformers |
Shen Ming,Yin Yi,Wu Jiandong,Wang Zhihao |
Shanghai Jiao Tong University Shanghai 200240 China |
|
|
Abstract The transformer is one of the most important equipment of the power system and the winding deformation is a main aspect leading to transformer failures. The paper adopts a simple but effective method to on-line monitor of the winding deformation. One of the 600kHz~1.2MHz sinusoidal signals is applied between one end of the winding and one ground terminal via the bushing along with power frequency signal. Then the line-end,neutral-end high frequency currents are continuously measured by the high frequency current sensor and the related analog and digital filtering technology is used to derive the injected sinusoidal signal of mixed signals. With the obtained line-end and neutral-end currents,the current offsets and current deviation coefficients are calculated to detect the extent,type and location of the winding deformation. The especially designed high frequency current sensor has advantages of a wide band,good linearity and high sensitivity. The experimental results show that the method can achieve the task of detecting the winding deformation and is able to distinguish the extent and type and the current deviation coefficients have a direct relationship with the location of the winding deformation. The method has a high sensitivity,good repeatability and strong anti-interference.
|
Received: 02 July 2013
Published: 22 January 2015
|
|
|
|
|
[1] 刘梦娜,彭发东,柯春俊,等. 变压器绕组变形故障的诊断分析[J]. 广东电力,2012,25(11): 108-111. Liu Mengna,Peng Fadong,Ke Chunjun,et al. Diagnosis analysis on transformer winding deformation failure[J]. Guangdong Electric Power,2012,25(11): 108-111. [2] Bagheri M,Naderi M S,Blackburn T,et al. On-line transformer winding deformation diagnosis: a profound insight to methods[C]. 26th International Power System Conference,2011: 1-14. [3] 吴立增,朱永利,苑津莎. 基于贝叶斯网络分类器的变压器综合故障诊断方法[J]. 电工技术学报,2005,20(04): 45-51. Wu Lizeng,Zhu Yongli,Yuan Jinsha. Novel method for transformer faults intigrted diagnosis on bayesian network classifier[J]. Transactions of China Electro- tecnical Society,2005,20(04): 45-51. [4] 王钰,李彦明,张成良. 变压器绕组变形检测的LVI法和FRA法的比较研究[J]. 高电压技术,1997,23(01): 13-15. Wang Jue,Li Yanming,Zhang Chengliang. The comparisonal study on LVI and FRA method of detecting winding deformation faults in transformers [J]. High Voltage Engineering,1997,23(01): 13-15. [5] Pham D A K,Pham T M T,Safari M H,et al. FRA-based transformer parameters at low frequencies [C]. IEEE International Conference on High Voltage Engineering and Application (ICHVE),2012: 476-479. [6] Florkowski M,Furgał J. Modelling of winding failures identification using the frequency response analysis (FRA) method[J]. Electric Power Systems Research,2009,79(7): 1069-1075. [7] 徐大可,汲胜昌,李彦明. 变压器绕组变形在线监测的理论研究[J]. 高电压技术,2000,26(03): 16-18. Xu Dake,Ji Shengchang,Li Yanming. A theorectical research on on-line monitoring of winding deformation of power transformer[J]. High Voltage Engineering,2000,26(03): 16-18. [8] 刘兴平,陈民铀. 一种配电变压器绕组变形故障的在线监测新方法[J]. 电力系统保护与控制,2013,41(12): 20-26. Liu Xingping,Chen Minyou. A novel method on on- line monitoring of winding deformation of transformers [J]. Power System Protection and Control,2013,41(12): 20-26. [9] Secue J,Mombello E. Sweep frequency response analysis(SFRA) for the assessment of winding displace- ments and deformation in power transformers[J]. Electric Power Systems Research,2008,78(6): 1119- 1128. [10] Joshi P M,Kulkarni S. Use of a deformation coefficient for transformer winding diagnostics[J]. International Journal of Emerging Electric Power Systems,2008,9(3): 1-15. [11] Satish L,Sahoo S K. Locating faults in a transformer winding: An experimental study[J]. Electric Power Systems Research,2009,79(1): 89-97. [12] Oguz Soysal A. A method for wide frequency range modeling of power transformers and rotating machines [J]. IEEE Transactions on Power Delivery,1993,8(4): 1802-1810. [13] Joshi P M,Kulkarni S V. A novel approach for on-line deformation diagnostics of transformer windings[C]. IEEE Power and Energy Society General Meeting,2010: 1-6. [14] Wang M,Vandermaar A J,Srivastava K. Improved detection of power transformer winding movement by extending the FRA high frequency range[J]. IEEE Transactions on Power Delivery,2005,20(3): 1930- 1938. [15] De Rybel T,Singh A,Vandermaar J A,et al. Apparatus for online power transformer winding monitoring using bushing tap injection[J]. IEEE Transactions on Power Delivery,2009,24(3): 996- 1003. [16] Setayeshmehr A,Borsi H,Gockenbach E,et al. On-line monitoring of transformer via transfer function [C]. Electrical Insulation Conference,2009: 278-282. [17] Setayeshmehr A,Akbari A,Borsi H,et al. New sensors for on-line monitoring of power transformer bushings [C]. Nordic Insulation Symposium,2005: 151-154. [18] Akbari A,Borsi H,Gockenbach E,et al. Experiences with a non-invasive capacitive sensor for on-line partial discharge detection in power transformers[J]. Diagnostik Elektrischer Betriebsmittel: Vorträge der ETG-Fachtagung am 09. und 10. März in Köln,2004,97: 301-304. [19] Joshi P,Kulkarni S. A diagnostic method for deter- mining deformations in a transformer winding: India,2009069145[P]. 2009-06-04. |
|
|
|