Abstract:A evaporative cooling power transformer with perfluorocarbon as coolant and dielectric is a new kind of power transmission and distribution equipment with smaller size, nonflammable and none plosive. While the perfluorocarbon used in the transformers is a new dielectric and it works under two-phase flow which differs from mineral oil, the monitoring and diagnostic method used for oil transformers is no longer suitable. To lay the foundation for safety operation and maintenance, as well as fault diagnosis, the decomposition products of fault conditions need to be analyzed. In this paper, decomposition products of perluorocarbon in a power arc have been analyzed by means of gas chromatograph/mass spectrometry(GC/MS) for identifying the decomposition products qualitatively and quantitatively. The amount of products formation rate vary with arc energy and arc current are studied. It is found that the formation rate is independent with arc energy, increase with arc current, however. Besides, the yield ratio nearly equal while arc energy and current change.
李康, 张国强, 牛文豪. 电弧故障下蒸发冷却变压器绝缘介质分解的实验研究[J]. 电工技术学报, 2013, 28(1增): 128-132.
Li Kang, Zhang Guoqiang, Niu Wenhao. Study of the Decomposition of Perfluorocarbon Used in Evaporative Cooling Transformers Under Power Arcs. Transactions of China Electrotechnical Society, 2013, 28(1增): 128-132.
[1] Zhang Feng, Zhang Guoqiang, Niu Wenhao, et al. Experimental study of the overheating decomposition products of fluorocarbon used in evaporative cooling transformers[C]. Proceedings of the 11th International Conference on Electrical Machines and Systems, 2008, (1-8): 844-846. [2] Niu Wenhao, Zhang Guoqiang, Jiang Yimin, et al. The experimental study of a novel cooling system of a power transformer in an urban underground substation[C]. Proceedings of the 2010 International Conference on Power System Technology, 2010: 1-6. [3] Niu Wenhao, Wang Xin, Guo Hui, et al. The AC breakdown voltage measurement of an evaporative coolant under two-phase-flow condition and its statistical analysis with weibull distribution and normal distribution[C]. Proceedings of the International Conference on Electrical Machines and Systems. 2007: 1820-1823. [4] Wang Xin, Niu Wenhao, Guo Hui, et al. AC breakdown voltage measurement of a fluorocarbon in gaseous state two-phase-flow state and liquid state[C]. Proceedings of the Electrical Insulation Conference and Electrical Manufacturing Expo, 2007: 91-93. [5] 巩学宾, 闫明发, 魏晶霞. 一例变压器内部故障的油色谱分析诊断和处理[J]. 高压电器, 2008, 44(3): 275-276. Gong Xuebin, Yan Mingfa, Wei Jingxia. Oil chromatogram analysis of a fault inside transformer[J]. High Voltage Apparatus, 2008, 44(3): 275-276. [6] 孔英会, 苑津莎, 李新叶, 等. 基于时序特征和参数估计的变压器故障诊断方法[J]. 电工技术学报, 2008, 23(12): 48-54. Kong Yinghui, Yuan Jinsha, Li Xinye, et al. A fault diagnosis method for power transformer based on temporal characteristics and parameter estimation[J]. Transactions of China Electrotechnical Society, 2008, 23(12): 48-54. [7] 张镱议, 廖瑞金, 杨丽君, 等. 基于云理论的电力变压器绝缘状态评估方法[J]. 电工技术学报, 2012, 27(5): 13-20. Zhang Yiyi, Liao Ruijin, Yang Lijun, et al. An assessment method for insulaiton condition of power transformer based upon cloud model[J]. Transactions of China Electrotechnical Society, 2012, 27(5): 13-20. [8] Li Kang, Xing Weijun, Zhang Guoqiang, et al. Study on decomposition gas for faults diagnostic of electrical equipment using fluorocarbons[C]. Proceedings of the 2010 International Conference on Power System Technology, 2010. [9] 陈伟根, 刘冰洁, 周恒逸, 等. 变压器油中溶解气体光声光谱检测的温度特性[J]. 电工技术学报, 2010, 25(11): 15-20. Chen Weigen, Liu Bingjie, Zhou Hengyi, et al. The temperature characteristics of photoacoustic spectroscopy detection for dissolved gases in transformer oil[J]. Transactions of China Electrotechnical Society, 2010, 25(11): 15-20.